FLEX I/Ot SCANportt Terminal Base (Cat. No. 1203 FB1) Installation Instructions 1 10 2 3 0 8 6 1 2 3 4 4 9 5 Channel 1 8 SCANport 7 FLEX I/O is a trademark of Allen Bradley Co. Inc. SCANport is a trademark of Allen-Bradley Co. Inc.
1–2 FLEX I/O SCANportt Base Installation Instructions Component Identification 1 Module locking latch 2 Keyswitch - Set to the position required for the installed module 3 Male flexbus connector (beneath the cover plug) 4 Cover plug for male flexbus connector 5 Key slot for attaching to 1203 module 6 Channel 2 SCANport connector 7 Locking tab for DIN rail 8 Channel 1 SCANport connector 9 Mounting holes for panel mounting 10 Female flexbus connector 1203-5.
FLEX I/O SCANportt Base Installation Instructions 1–3 Mounting on a DIN Rail DIN Rail Locking Lever (D) B C Side View 8 9 0 1 6 4 2 3 A D ATTENTION: Do not remove or replace a terminal base unit when ! power is applied. Interruption of the flexbus can result in unintended operation or machine motion. 1. Remove the cover plug (if used) in the male connector of the unit to which you are connecting this terminal base unit. 2.
1–4 FLEX I/O SCANportt Base Installation Instructions 6. Press the terminal base down onto the DIN rail until flush. The locking lever D snaps into position and locks the terminal base to the DIN rail. 7. If the terminal base does not lock in place, use a screwdriver or similar device to move the locking lever down, press the terminal base flush with the DIN rail, and release the locking lever to lock the base in place. 8.
FLEX I/O SCANportt Base Installation Instructions 1–5 Wiring To wire the 1203–FB1 base, connect a SCANport cable from the SCANport device to the desired channel. SCANport cables are available in either Male–to–Male or Male–to–Female configurations. You can connect cables of up to 10 meters (33 feet) between a SCANport device and any SCANport peripheral.
1–6 FLEX I/O SCANportt Base Installation Instructions European Union Directive Compliance If this product has the CE mark it is approved for installation within the European Union or EEA regions. It has been designed and tested to meet the following directives.
With major offices worldwide. World Headquarters, Allen Bradley 1201 South Second Street Milwaukee, WI 53204 USA Tel: (1) 414 382 2000 Fax: (1) 414 382 4444 Publication 1203 5.7ML - April 1996 PN95654101 Copyright 1996 Allen Bradley Company, Inc.