User Manual

1 Publicatio n 1000-UM001B-US-P - July 20 00
Chapter
5
Troubleshooting Guide
Troub leshooting Guide
Table 5.A SLS Box
Problem Component Possible Cause Check Suggested Action Repairable?
Low voltage on
sec ondary
Low voltage on
primary
Control
transformer
Loose
connections,
System voltage
Prim ar y wired f or prop er
voltage
Replace if nothing suspicious
found.
No
High voltage on
secondary
Primary wi red
wrong
Voltage on input Replace if nothing suspicious
found.
No
Blown fuse
indicated
Primary f uses Overload or short
in CCT
For c orrec t w iring or
fault in control circuit
Rep lace CCT if necessary and
install correct size fuse as
shown on the wiring diagram.
Blown fuse
indicated
Secondary f use Overload or short
in CCT
For c orrec t w iring or
fault in control circuit
Rep lace CCT if necessary and
install correct size fuse as
shown on the wiring diagram.
Low DC voltage on
load side
Pow er supp ly Overload, low
vo ltag e on AC
side
Ad just outp ut vo ltag e,
Check CCT voltage
output.
Rep lace if defective. No
Does not pick up Contactor Low voltage Control voltage
Open coil Flash light coil Replace entire assembled
contactor.
No
Open in coil
circuit
Entire coil ci rcuit
Fo r ei g n ma terial
jam
Replace entire assembled
contactor.
No
Does not drop out Welded contact
or fore i gn
material jam
Coil voltage must be
zero.
Replace entire assembled
contactor.
No
Con tinuity or
non-operation
Auxili ary contacts Resistance of contacts
with wires removed
Auxiliary contacts are locked
on the conta c to r replace entire
assembled device.
No
Sa fety c on tacts
betw een termi nal
#13 and #14 will
not close and there
is no voltage on
load side of
co nt actor an d I C
auxi lia ry is closed
VSR Bad relay Refer to VSR literature
and LEDs on front of
VSR for status .
Replace VS R. No