Instruction Manual

VIVA 4W LED MAINTAINED EMERGENCY EXIT BOX,
SELF TEST, LIFEPO4 BATTERY
R4EMLEDST-01
PLEASE READ INSTRUCTION BEFORE COMMENCING INSTALLATION AND RETAIN FOR FUTURE REFERENCES.
! Electrical products can cause death or injury, or damage to property. If in any doubt about the installation or use of this product,
consult a competent electrician
Note:
Product technical information and specification may change over time without prior notification. For the latest technical information
please visit our web site www.robus.com.au
0°C < Ta < +40°C, 220-240V~50/60Hz, Class II, IP20, Battery warranty 3 years, Luminaire is non-dimmable
LED Group
Crowe Hogwarth Tel: +64 3668 5285
72 Trafalgar Square Email: nz_purchases@robus.com
NELSON 7010 Website: www.robusled.co.nz
New Zealand
Issue 1 160320
Installation
1. Ensure mains supply is switched off before
commencing installation.
2. Remove the PC tray from the body of fitting and
remove the cover of terminal from the PC tray by
removing the screw as per fig 2.
3. Knock out the intended cable entry hole suitable
for your installation.
4. Mark appropriate fixing points on wall or ceiling;
check that fixings will not impinge on concealed
cables or pipes before drilling holes.
5. Fix the PC tray to ceiling/wall using suitable screws.
6. Connect wires from unswitched supply to terminals
on gear tray, Brown to PL, Blue to N and
green/yellow to Earth. There is a link between
switched live (SL) and permanent live (PL)
terminals (maintained). LEDs controlled by switch,
connect switched live wire to terminal SL and
permanent live to PL. Note: if “SL” terminal not
connected, fitting works as non-maintained.
7. Write installation date on battery.
8. Insert the legends on to diffuser.
9. Attach the body of fitting on to the PC tray.
Switch on supply: The green LED should come on
indicating correct battery charge status. When supply
to permanent live PL is lost, battery will operate fitting
in emergency mode. Interrupt supply by pressing the
test switch, the fitting will then operate in emergency
mode for a short period of time.
Note: This luminaire has no user serviceable parts. If
damaged, disconnect from mains and discontinue use.
LED Group Australia Pty Limited
Suite B, 2 Pittwin Road Tel: 07 3890 5444
Capalaba Fax: 07 3890 4777
Queensland 4157 Email: purchases@robus.com
Australia Website: www.robus.com.au
Testing
The emergency lighting must be inspected and
tested regularly in accordance with local codes
of practice: note: for safety reasons tests should
be carried out during daylight hours.
The minimum recommended test schedule is as
follows:
After installation, allow 24 hours to ensure full
battery charge and then interrupt the supply; the
maximum duration time is 90 minutes check that
LEDs are still lighting.
1. Daily check that charge indicator LED is
working.
2. Monthly, interrupt mains for a short period and
check LED lights.
3. Annual 12 month check, full duration test.
Interrupt mains supply, LEDs will light and
should last for a minimum 90 minutes
operation: batteries must be replaced when
they can no longer support 90 minutes
operation.
4. Complete record sheet on installation and
retain in maintenance file.
5. Update file with ongoing test records for
inspection by fire officer or other duly
authorised person.