Technical data

66
With reference to Table 6.1 Gas type identication values 15. 67 and the fumes
analyser reading, check that the CO
2
content percentage of the combustion pro-
ducts is within ±0,2 of the characteristic value for the gas being used.
If the value is in the correct range, go to step "17". Otherwise, remove the side 16.
panel (N) and follow the instructions given in steps "25" and "26", including the
note, in the procedure given in Paragraph 6.3 CHANGE OF GAS TYPE 70.
Enter menu 2 and execute action "23": timed forcing of the appliance to mini-17.
mum power (8.0 kW). The procedure to run the actions of menu 2 is specied
in this Paragraph Step 2".
With reference to Table 6.1 Gas type identication values 18. 67 and the fumes
analyser reading, check that the dierence between the CO
2
percentage obser-
ved in step “15” and the current reading corresponds to the delta CO
2
characte-
ristic of the gas being used.
Example: having set, in step "15", a CO
2
content of 9.5% for G20 gas, at step "18" the
reading should be 9.0% (=9.5%-0.5%).
If the dierence satises the delta CO19.
2
requirement, go to the next step. Other-
wise, follow the instructions given in steps "30" and "35", including the note, in
the procedure given in Paragraph 6.3 CHANGE OF GAS TYPE 70.
Enter menu 2 and execute action "25": forced stop to cancel the preceding for-20.
ced operation and return to the initial operational conguration.
After 30 minutes of operation the appliance automatically cancels the preceding for-
ced power mode. To anticipate this timing, select and execute action "25" in menu 2.
Switch o and completely restore the appliance.21.
Figure 6.1 – Checking and adjusting the combustion parameters
Procedure for checking and adjusting the combustion parameters.
LEGEND
E front panel interior
F access hole for OFFSET regulator
G access hole for ow rate regulator
H front panel exterior
L access plug for ow rate regulator
M access plug for OFFSET regulator
N external side panel