Technical data
Installation, user and maintenance manual – GAHP-A
69
8   APPENDIX
8.1   MACHINE OPERATING CODES
Table 8.1 – TABLE OF OPERATING CODES generated by S61 controller (rmware version 3.015)
CODES DESCRIPTION TRIP CONDITIONS RESET METHOD
E 400
FAULT ON RESET CIRCUIT OF FLAME 
CONTROL UNIT
Fault on reset circuit of ame control unit. Contact authorised Robur TAC.
u 401
GENERATOR LIMIT TEMPERATURE 
THERMOSTAT
High temperature detected by limit thermostat 
on body of generator
Reset limit thermostat manually: operation will be restored 
automatically when the cause ceases.
E 401
GENERATOR LIMIT TEMPERATURE 
THERMOSTAT
U 1 code active for 1 hour, or U 1 code generated 
3 times in 2 hours of operation.
Contact authorised Robur TAC.
u 402 FUMES THERMOSTAT
High temperature detected by exhaust fumes 
thermostat
Reset occurs automatically when the condition that generated the 
code ceases, with hysteresis of 8 °C
E 402 FUMES THERMOSTAT
u 2 code active for 1 hour, or u 2 code generated 
3 times in 2 hours of operation.
Reset may be performed from the CCI/DDC (or from the S61 board 
via menu 2, parameter 21). If codes u 2 and/or E 2 occur again, 
contact authorised Robur TAC.
E 405 HIGH AMBIENT TEMPERATURE
HIGH temperature detected by ambient 
temperature sensor.
Reset occurs automatically when the condition that generated the 
code ceases.
E 406 LOW AMBIENT TEMPERATURE
LOW temperature detected by ambient 
temperature sensor.
Reset occurs automatically when the condition that generated the 
code ceases.
u 407
HIGH CONDENSER INLET 
TEMPERATURE
HIGH temperature detected by condenser inlet 
temperature sensor or fumes sensor.
Reset occurs automatically when the condition that generated the 
code ceases.
E 407
HIGH CONDENSER INLET 
TEMPERATURE
u 7 code active for 1 hour, or u 7 code generated 
12 times in 2 hours of operation.
Carry out appropriate checks. Reset may be performed from the 
CCI/DDC (or from the S61 board via menu 2, parameter 21). If the 
code persists, contact authorised Robur TAC.
E 408 FLAME CONTROL UNIT ERROR
E 12 on unit and condenser inlet temperature 
increasing by over 10 °C within 1 hour.
Carry out appropriate checks. Reset may be performed from the 
CCI/DDC (or from the S61 board via menu 2, parameter 21). If the 
code persists, contact authorised Robur TAC.
u 410 INSUFFICIENT HOT WATER FLOW
Insucient water ow (the circulator is on and 
the owmeter measure a low water ow).
Reset occurs automatically when correct water ow is restored.
E 410 INSUFFICIENT HOT WATER FLOW
u 10 code is repeated, or code u 10 is active for 
1 hour
Reset may be performed from the CCI/DDC (or from the S61 board 
via menu 2, parameter 21). If the code persists, contact authorised 
Robur TAC.
u 411
INSUFFICIENT ROTATION OF OIL 
PRESSURE PUMP
Insucient rotation of oil pressure pump. Reset occurs automatically 20 minutes after the Code is generated.
E 411
INSUFFICIENT ROTATION OF OIL 
PRESSURE PUMP
u 11 code generated twice in 2 hours of 
operation.
Reset may be performed from the CCI/DDC (or from the S61 board 
via menu 2, parameter 21). If the code persists, contact authorised 
Robur TAC.
u 412 FLAME CONTROL UNIT ARREST Failure to ignite burner.
Reset occurs automatically when the solenoid valve opens again 
(new attempt at ignition), or after code is active for 5 minutes.
E 412 FLAME CONTROL UNIT ARREST Flame arrest signal.
Reset may be performed from the CCI/DDC (or from the S61 board 
via menu 2, parameter 20). If the code persists, contact authorised 
Robur TAC.
E 416
HOT OUTLET WATER TEMPERATURE 
SENSOR DEFECTIVE
Fault (interruption or short circuit) on hot outlet 
water temperature sensor.
Reset may be performed from the CCI/DDC (or from the S61 board 
via menu 2, parameter 21). If the code persists, contact authorised 
Robur TAC.
E 417
COLD INLET WATER TEMPERATURE 
SENSOR DEFECTIVE
Fault (interruption or short circuit) on inlet water 
temperature sensor.
Reset may be performed from the CCI/DDC (or from the S61 board 
via menu 2, parameter 21). If the code persists, contact authorised 
Robur TAC.
E 420
CONDENSER INLET TEMPERATURE 
SENSOR DEFECTIVE
Fault (interruption or short circuit) on condenser 
inlet temperature sensor.
Reset may be performed from the CCI/DDC (or from the S61 board 
via menu 2, parameter 21). If the code persists, contact authorised 
Robur TAC.
E 422 WATER FLOWMETER FAULT Water owmeter fault
Reset may be performed from the CCI/DDC (or from the S61 board 
via menu 2, parameter 21). If the code persists, contact authorised 
Robur TAC.
E 423 AIR/GAS MIXTURE SENSOR FAULT Air gas mixture sensor fault
Reset may be performed from the CCI/DDC (or from the S61 board 
via menu 2, parameter 21). If the code persists, contact authorised 
Robur TAC.
E 424
FUMES TEMPERATURE SENSOR 
FAULT
Fumes temperature sensor fault
Reset may be performed from the CCI/DDC (or from the S61 board 
via menu 2, parameter 21). If the code persists, contact authorised 
Robur TAC.
E 428
GAS SOLENOID VALVE EXCITED 
DURING FLAME CONTROLLER 
ARREST
The ame controller is arrested (E 12) but the gas 
solenoid valve is excited. In this case the ame 
controller is de-excited (E 12 resets).
Reset may be performed from the CCI/DDC (or from the S61 board 
via menu 2, parameter 21). If the code persists, contact authorised 
Robur TAC.
u 429
GAS SOLENOID VALVE WITHOUT 
ELECTRICAL POWER
Gas solenoid valve is o for 5 seconds (with 
central ame control unit on).
Reset occurs automatically if the gas solenoid valve switches on 
again within 10 minutes (with central ame control unit on).
E 429
GAS SOLENOID VALVE WITHOUT 
ELECTRICAL POWER
Code U 29 is active for more than 10 minutes 
(with ame controller unit on).
Carry out appropriate checks. Reset may be performed from the 
CCI/DDC (or from the S61 board via menu 2, parameter 21). If the 
code persists, contact authorised Robur TAC.
E 436 BLOWER FAULT Blower fault
Reset may be performed from the CCI/DDC (or from the S61 board 
via menu 2, parameter 21). If the code persists, contact authorised 
Robur TAC.
E 437
LOW COMBURENT AIR 
TEMPERATURE
Air comburent temperature equal or smaller of 
-10 °C
Reset occurs automatically when the condition that generated the 
code ceases.