Technical data

56
How to connect the plant water circulation pump
For how to connect the system pumps, see the section with this title in Paragraph 5.3
TYPE B (DDC) 43.
5.5 HOW TO REMOTELY CONTROL THE FLAME CONTROLLER RESET
The ame controller reset can be controlled remotely by installing a button (not sup-
plied) to the ame controller inside the unit’s electrical panel.
Connect the button as instructed below.
You will need: the appliance disconnected from the electricity supply
The cable required to connect the reset button must be 3x0.75mm1.
2
.
Cut a suitable length of cable.2.
Connect the cable to the blind terminals A (see Figure 5.18 Button connection for 3.
ame controller reset 57).
The cable may not be longer than 20 metres.
Incorrect wiring of the reset button may damage the component irreparably. Check the
cabling carefully before powering the unit.