Technical data
56
How to connect the plant water circulation pump
For how to connect the system pumps, see the section with this title in Paragraph 5.3
TYPE B (DDC) → 43.
5.5 HOW TO REMOTELY CONTROL THE FLAME CONTROLLER RESET
The ame controller reset can be controlled remotely by installing a button (not sup-
plied) to the ame controller inside the unit’s electrical panel.
Connect the button as instructed below.
You will need: the appliance disconnected from the electricity supply
The cable required to connect the reset button must be 3x0.75mm1.
2
.
Cut a suitable length of cable.2.
Connect the cable to the blind terminals A (see Figure 5.18 Button connection for 3.
ame controller reset → 57).
The cable may not be longer than 20 metres.
Incorrect wiring of the reset button may damage the component irreparably. Check the
cabling carefully before powering the unit.