Technical data
Installation, user and maintenance manual – GAHP-A
55
the opening of the appliance's consent switch contacts, the circulation pump will thus 
continue to circulate the water in the plant for a further 10 minutes, thereby ensuring the 
complete dispersal of the heating energy produced.
When the pump is controlled by the appliance's controller, this delay is automati cally ap-
plied by the board.
5.4   TYPE C CONSENT SWITCH
In this type of installation and control, the system pump does not vary the ow rate.
Before making the electrical connections, make sure that work is not carried out on live 
elements.
General indications
 Check that the power supply voltage is 230 V 1N - 50 Hz power.•
 Make the electrical connections as given in the following wiring diagrams.•
 Make the electrical connection in such a way that the ground wire is longer than •
the live wires. In this way it will be the last wire to be pulled away if the mains cable 
should accidentally be pulled, and will thus guarantee the ground connection.
The electrical safety of the appliance is guaranteed only when it is correctly connected 
to an ecient grounding system, executed in accordance with current safety regulations. 
Do not use gas pipes to ground electrical appliances.
How to connect the consent switch
You will need: the appliance is not powered electrically (external master power switch 
set to OFF)
 Connect the consent switch (on-o switch or ambient thermostat or timer, etc.) to 1. 
terminals R and W on the appliance’s control circuit as shown in Figure 5.17 Electri-
cal wiring diagram → 55 (detail “CS”).
For the appliance to operate correctly, it is ALWAYS necessary to provide a consent switch. 
Do not use the general mains external circuit breaker («GS») to switch the appliance on 
or o.
Figure 5.17 – Electrical wiring diagram
electrical connections of ON/OFF command switch
LEGEND
SCH   Electronic board
R
   Common
W   Terminal consensus warming
Components NOT SUPPLIED
CS
   ON/OFF command switch