Technical data

36
Figure 4.4 – Fume outlet
LEGEND
A Curve 90° Ø 80
B
Pipe Ø 80 Lg.300 mm w/terminal
C rain cover
4.8 PROGRAMMING OF HYDRAULIC PARAMETERS
The operations described in this paragraph are necessary only if the appliance is not con-
nected to a DDC or to a CCP.
If the appliance is connected to a DDC, follow the instructions given in the DDC manuals
exclusively.
This paragraph explains how to set the hydraulic parameters on the electronic board
of the appliance. Users not familiar with the basic procedures for the use of the board
should refer to Paragraph 3.2 ON-BOARD ELECTRONICS 19.
To congure the appliance, access menu 3 of the electronic board.
With regard to the hydraulic conguration, six parameters may be set: select the letter E
to exit to the previous menu.
Table 4.3 – Menu 3 parameters
HYDRAULIC PARAMETER THE DISPLAY SHOWS
Hot water thermostat control selection 3.160
Hot water setpoint 3.161
Hot water temperature dierential 3.162
(EXIT MENU) 3. E
Description of parameters:
Select water thermostating, parameter 160: this parameter may have two values, 0 •
or 1. When the user chooses:
·0: the temperature that aects the activation and deactivation of the appliance is de-
tected by the sensor on the INLET water, i.e. water owing into the appliance.
·1: the temperature that aects the activation and deactivation of the appliance is de-
tected by the sensor on the OUTLET water, i.e. water owing out of the appliance.