Technical data

22
Table 3.3 – Menu 2
ACTION REQUIRED FOR EXECUTION SHOWN ON DISPLAY AS
20 Reset ame controller arrest 2. 20
21 Reset other operating codes 2. 21
22 Manual defrost 2. 22
23 Timed forcing to minimum power 2. 23
24 Timed forcing to maximum power 2. 24
25 Regulation of power 2. 25
E (EXIT MENU) 2. E
The general operating codes of the controller can be reset with functions "20" and "21".
Actions "23", "24" and "25" are used to regulate the combustion parameters or for gas type
changeovers, and are thus for use only by the installation technician or Robur TAC (for
other information refer to Paragraph 6.1 PROCEDURE FOR INITIAL ACTIVATION 59).
ACTION "20"
Reset ame controller arrest; this may be used when the appliance is rst activated, see
Paragraph 3.1 START UP (AND SHUT DOWN) 17, when the appliance is in a permanent
locked condition or after a long period of disuse (see Paragraph 3.5 PROLONGED PERI-
ODS OF DISUSE 23).
You will need: access to the electrical panel, see Paragraph "Display and knob".
To reset the ame control unit select menu 2, as indicated in the Paragraph "Accessing
the Menus"; then proceed as follows:
The display shows: "2." press the knob to access the menu. The display initially 1.
shows item "2. 20".
Press the knob to display the ashing reset request: "reS1".2.
Press the knob again to reset the ame controller. The reset request stops ashing, 3.
and again the display shows "2. 20". The reset operation has been performed.
To quit the menu, turn the knob clockwise until the "2. E" is displayed. Now press 4.
the knob to return to menu selection: "2.".
To exit the menu selection and return to the normal visualisation of the parameters 5.
of the appliance, turn the knob clockwise until "E" displays; press the knob to quit.
ACTION "21"
Reset other warnings/errors; this is required to reset any warnings and er rors that may
occur during operation of the appliance.
You will need: access to the electrical panel, see Paragraph “Display and knob.
To reset the controller errors, select menu 2, as indicated in the Paragraph "Accessing the
Menus"; Then:
The display shows: "2." press the knob to access the menu. The display initially 1.
shows item "2. 20".
Turn the knob clockwise to display item "2. 21".2.
Press the knob to display the ashing reset request: "rEr1".3.
Press the knob again to perform a board error reset. The reset request stops ash-4.
ing, and the again display shows "2. 21". The reset operation has been performed.
To quit the menu, turn the knob clockwise until the "2. E" is displayed. Now press 5.
the knob to return to menu selection: "2.".
To exit the menu selection and return to the normal visualisation of the parameters 6.
of the appliance, turn the knob clockwise until "E" displays; press the knob to quit.
ACTION "22"