2.3 TECHNICAL MANUFACTURING CHARACTERISTICS
The appliance is supplied with the following technical manufacturing characteristics,
control and safety components:
Steel sealed circuit, treated on the outside with epoxy paint.•
Sealed combustion chamber suited for type C installation.•
Metal mesh irradiation burner equipped with ignition and ame detection man-•
aged by an electronic control unit.
Tube coil heat recovery (AISI 304L ).•
Air-based heat exchanger with single-position nned coil, manufactured in steel •
tubing and aluminium ns.
Titanium stainless steel tube bundle water exchanger, with external insulation.•
Automatic two-way microprocessor-controlled defrosting valve, allowing the •
nned coil to be defrosted.
Control and safety components
S61 controller with integrated microprocessor and LCD display and control knob, •
complete with "Mod10" supplementary combustion modulation controller (see
Figure 5.1 Electronic board S61 → 39 and Figure 5.2 Mod10 controller → 41).
Plant water owmeter.•
Sealed circuit high temperature limit thermostat, manual reset.•
Flue temperature limit switch, automatic reset.•
Flue temperature thermostat 120 °C, manual reset.•
Sealed circuit safety relief valve.•
Safety by-pass valve, between high and low pressure sealed circuit.•
Antifreeze function for hydronic system.•
Ionization ame control box.•
Double shutter electric gas valve.•
Condensate siphon icing sensor.•
2.4 TECHNICAL DATA
Table 2.1 – GAHP-A LT technical data
GAHP-A LT GAHP-A LT S
OPERATION WHEN HEATING
OPERATING POINT A7W50
G.U.E. gas usage eciency % 151 (1)
Thermal power kW 34,9 (1)
OPERATING POINT A7W35
G.U.E. gas usage eciency % 165
Thermal power kW 38,4
Thermal capacity
Nominal (1013 mbar - 15°C) kW 25,7
true peak kW 25,2
NOx emission class 5
NOx emission ppm 25
CO emission ppm 36
Hot water delivery temperature
maximum for heating °C 55
maximum for ACS °C 70
Hot water return temperature
maximum heating °C 45
maximum for ACS °C 60
minimum °C 2
Hot water ow rate
nominal l/h 3000
maximum l/h 4000
minimum l/h 1000
Hot water pressure drop
nominal water pressure
(A7W50)
bar 0,43 (2)
Ambient air temperature (dry bulb)
maximum °C 45
minimum °C -20 (7)
Thermal dierential nominal °C 10