User`s guide
APPENDIX
Ed. 04/2012
85
U
12
FLAME CONTROL UNIT ARREST
CODE GENERATED BY: Failure to ignite burner.
RESET METHOD: Reset occurs automatically when the electrovalve opens again (new attempt at ignition), or after code is
active for 5 minutes.
E 12
FLAME CONTROL UNIT ARREST
CODE GENERATED BY: Flame arrest signal.
RESET METHOD: Reset may be performed via DDC (or S61 board via menu 2, parameter 0). If the code persists, contact
authorised Robur TAC.
E 16
OUTLET WATER TEMPERATURE SENSOR DEFECTIVE
CODE GENERATED BY: Fault (interruption or short circuit) on outlet water temperature sensor.
RESET METHOD: Reset may be performed via DDC (or S61 board via menu 2, parameter 1). If the code persists, contact
authorised Robur TAC.
E 17
COLD INLET WATER TEMPERATURE SENSOR DEFECTIVE
CODE GENERATED BY: Fault (interruption or short circuit) on condenser outlet temperature sensor.
RESET METHOD: Reset may be performed via DDC (or S61 board via menu 2, parameter 1). If the code persists, contact
authorised Robur TAC.
E 18
CONDENSER OUTLET TEMPERATURE SENSOR DEFECTIVE
CODE GENERATED BY: Fault (interruption or short circuit) on condenser inlet temperature sensor.
RESET METHOD: Reset may be performed via DDC (or S61 board via menu 2, parameter 1). If the code persists, contact
authorised Robur TAC.
E 20
CONDENSER INLET TEMPERATURE SENSOR DEFECTIVE
CODE GENERATED BY: Fault (interruption or short circuit) on condenser inlet temperature sensor.
RESET METHOD: Reset may be performed via DDC (or S61 board via menu 2, parameter 1). If the code persists, contact
authorised Robur TAC
E 28
GAS ELECTROVALVE ON IN CASE OF FLAME CONTROL UNIT ARREST
CODE GENERATED BY: Flame control box is in arrest mode (E12) and the gas electrovalve is ON. In this condition the flame
control box is switched in OFF (E12 enabled).
RESET METHOD: The reset can be done via DDC (or S61 electronic board menu 2, parameter 1). If the code error persist
contact Robur personnel.
U
29
GAS ELECTROVALVE WITHOUT ELECTRICAL POWER
CODE GENERATED WHEN: Gas electrovalve is off for 5 seconds (with central flame control unit on).
RESET METHOD: Reset occurs automatically if the gas electrovalve switches on again within 10 minutes (with central flame
control unit on).
E 29
GAS ELECTROVALVE WITHOUT ELECTRICAL POWER
CODE GENERATED WHEN: Code
U
29 is active for more than 10 minutes (with central flame control unit on).
RESET METHOD: Carry out appropriate checks. Reset may be performed via DDC (or S61 board via menu 2, parameter 1).
If the code persists, contact ROBUR TAC.
U
51
ANTIFREEZE FUNCTION ACTIVATED – COOLING MODULE
Activation takes place only if the circulator is off and the antifreeze function is enabled (see menu 1, parameter 77).
CODE GENERATED WHEN: Inlet or outlet water temperature of the cold module falls below 4°C (the code generated signals that the
antifreeze function has been activated).
In this case the antifreeze function activates the plant water circulator.
RESET METHOD: Reset (deactivation of antifreeze function) occurs automatically when, with only the circulator on, the inlet
and outlet water temperatures return to over 5°C (in this case the circulator switches off), or if the function
itself is disabled.