User`s guide
ACF60-00 – Installation, User’s and Maintenance Manual
62
Ed. 04/2012
For a total distance of ≤ 200 m and a network with a maximum of 6 nodes (typical
example: up to 5 ACF60-00’s + 1 DDC) a simple 3x0.75 mm shielded cable can be
used.
Calculate the length necessary for the current installation, then purchase the correct
cable.
As seen in the table, the CAN connection requires a 3 wire CAN BUS cable. If the cable
being used has more than 3 coloured wires, choose the colours to be used and cut the
unnecessary wires.
The ROBUR NETBUS cable is available as an accessory, see “ACCESSORIES” on page
81.
Connection of the CAN BUS cable to the ACF
Requirements: The ACF (or ACF's) must be positioned in its final location.
To connect a CAN BUS cable to an ACF:
The CAN BUS cable is connected to the appropriate connector on the S61 electronic
circuit board on the ACF, see Figure 11, page 31 as well as the figure below. Proceed as
indicted below.
Figure 26 – Connection example of CAN BUS cable
KEY
A Protective isolating tape
B Shielding of CAN BUS cable
(pre-wired to last unit)
C Cable bracket (the CAN
BUS cables of an
intermediate node are
present)
D CAN BUS/circuit board
connector
E Wires (6) of the CAN BUS
cable (intermediate node)
A
A
B
C
E
D