User`s guide

Section GENERAL INFORMATION AND TECHNICAL SPECIFICATIONS
Ed. 04/2012
25
PED Characteristics
The ACF60-00 chiller has a pressurized hermetic circuit and is therefore subject to the to
the Pressurized Equipment Directive (PED).
The corresponding parameters and value are reported in the following table:
ACF60-00
ACF60-00 HR
ACF60-00 TK ACF60-00 HT
ACF60-00 LB
PARAMETERS FLUID CONTENT CHARACTERISTICS
FLUID CONTENT
H
2
O + NH
3
CHARGE
kgH
2
O
kgNH
3
10
7.5
10
7.5
10
8.5
10.5
7.5
10.5
7.2
FLUID GROUP
PRESSURE
MAXIMUM
ALLOWABLE
PRESSURE
bar
35
SAFETY VALVE
CALIBRATION
PRESSURE
bar
35
TEST PRESSURE
(in air)
bar
55
VOLUME
GENERATOR litres
18.6
LEVELING
CHAMBER
litres
11.5
SOLUTION PUMP litres
3.3
SCA litres
6.3
EVAPORATOR litres
3.7
RECOVERY UNIT litres
3.7
COOLANT
VOLUME
VARIATOR
litres
4.5
TARE AND FILLING RATIO
TARE kg kg
220 230
FILLING RATIO
kg(NH
3
)/
L
0.173 0.159 0.177 0.157 0.150