User`s guide

ACF60-00 – Installation, User’s and Maintenance Manual
22
Ed. 04/2012
Table 13 ACF60-00 HR, ACF60-00 HR S – Cooling capacity multiplication correctional factors in air conditioning +
heat recovery mode for external air temperatures and water flow rates different from the nominal values
reported in the table.
ACF60-00 HR, ACF60-00 HR S – HEATING CAPACITY OF THE HEAT RECOVERY
UNIT in kW (chilled water delivery temperature 7.2 °C, output AT THE HEAT
RECOVERY UNIT variable)
Table 14 Heat capacity of the heat recovery unit in relation to the temperature (T) of the water returning to the heat
recovery unit and the T of the external air. Temperature values for chilled water delivery = 7.2°C, output =
500 L/hr. Empty grey boxes: outside operational range
OPERATIONAL MODE: AIR CONDITIONING + HEAT RECOVERY
WATER DELIVERY TEMPERATURE °C
EXTERNAL AIR
TEMPERATURE
°C
3.0 5.0 7.0 9.0
0
0.97 0.98 1.00 1.02
5
0.97 0.98 1.00 1.02
10
0.97 0.98 1.00 1.02
15
0.97 0.98 1.00 1.02
20
0.97 0.98 1.00 1.02
25
0.96 0.98 1.00 1.02
30
0.89 0.97 1.00 1.02
35
0.73 0.91
1.00
1.02
40
0.89 0.95 0.96
45
0.80 0.85
HEAT CAPACITY kW (Output = 500 L/hr)
EXTERNAL AIR TEMPERATURE
°C
RECOVERY
SYSTEM HOT
WATER RETURN
TEMPERATURE
°C
15 20 25 30 35 40 45
10
27.00 27.20 27.43 27.50 27.90 28.20 28.50
20
21.30 22.00 22.54 23.00 23.48 24.40 25.00
30
15.41 16.30 17.15 18.05 19.08 20.08 21.15
40
10.50 11.50 12.30 13.49 14.92 16.30 18.01
50
6.40 7.10 8.01 9.30 11.00 12.80 14.88
60
2.80 3.58 4.50 5.50 7.33 9.20 12.00
70
2.40 2.63 4.05 6.15 8.90