ACF60-00 HR, ACF60-00 HR S - TECHNICAL SPECIFICATIONS
SIZE
UNIT
ACF60-00
HR
ACF60-00
HR S
OPERATIONAL CHARACTERISTICS
NOMINAL HEAT CAPACITY AT THE BURNER
(1)
NOMINAL
EFFECTIVE
kW
25.30
25.03
COOLING CAPACITY
(AIR CONDITIONING ONLY – NO RECOVERY)
(2)
kW 17.72
COOLING CAPACITY
(AIR CONDITIONING + RECOVERY)
(3)
kW 17.93
CHILLED WATER FLOW RATE
NOMINAL
MINIMUM
MAXIMUM
L/hr
2770
2500
3200
m
3
/h
GAS CONSUMPTION NAT. GAS
(4)
L.P.G.
(5)
NOMINAL
EFFECTIVE
NOMINAL
EFFECTIVE
kg/hr
2.68
2.65
1.96
1.94
NOISE LEVEL
(6)
(7)
at 10 meters MAXIMUM dB(A) 54 49
FUNCTIONAL RANGE (T
OUTSIDE AIR
)
MINIMUM
MAXIMUM
°C
0
+45
ACF INTAKE WATER TEMPERATURE MAXIMUM °C +45
OUTLET WATER TEMPERATURE MINIMUM °C +3
HEAT RECOVERY SYSTEM SPECIFICATIONS
HEAT CAPACITY
(8)
kW 21
RECOVERY SYSTEM HOT WATER FLOW RATE (∆T=18°C
(8)
) L/hr 1000
PRESSURE DROP INSIDE RECOVERY SYSTEM NOMINAL
m
CA
bar
1.3
0.12
ELECTRICAL CHARACTERISTICS
VOLTAGE
V, phases,
Neutral, Hz
230 1N 50
TOTAL ELECTRICAL LOAD
(9)
W 820 870
WATER CONNECTIONS
CHILLED WATER DELIVERY AND RETURN 1 ¼ “F
RECOVERY WATER DELIVERY AND RETURN 1 ¼ “F
GAS ¾ “F
ACF INTERNAL PRESSURE DROP (cooling circuit )
(10)
NOMINAL bar 0.29
PRESSURE DROP (heat recovery circuit)
(11)
See Figure 5 page 24
MAXIMUM WORKING PRESSURE bar 4
MAXIMUM FILLING PRESSURE bar 3
PHYSICAL SPECIFICATIONS
OPERATIONAL WEIGHT kg 370 390
WATER CAPACITY OF ACF CHILLER ONLY L 3
WATER CAPACITY OF HEAT RECOVERY SYS. L 3
WIDTH
850
DEPTH
1230
DIMENSIONS
HEIGHT
mm
1290 1540
(12)