User`s guide

Section GENERAL INFORMATION AND TECHNICAL SPECIFICATIONS
Ed. 04/2012
19
ACF60-00 LB, ACF60-00 LB S – COOLING CAPACITY CORRECTION FACTORS – 2/2
Table 10 ACF60-00 LB, ACF60-00 LB S – 2/2 - Cooling capacity correctional multiplication factors for external air
temperatures and water flow rates different from the nominal values reported in the table.
WATER DELIVERY TEMPERATURE °C
EXTERNAL AIR
TEMPERATURE
°C
-10.0 -7.0 -5.0 -2.0 0
27
1.04 1.07 1.10 1.13 1.15
28
1.02 1.06 1.09 1.12 1.15
29
1.01 1.05 1.08 1.11 1.14
30
0.99 1.03 1.07 1.10 1.14
31
0.97 1.02 1.06 1.09 1.13
32
0.95 1.00 1.05 1.08 1.12
33
0.93 0.98 1.03 1.07 1.11
34
0.90 0.96 1.02 1.06 1.10
35
0.88 0.94 1.00 1.04 1.08
36
0.85 0.92 0.98 1.02 1.07
37
0.82 0.89 0.96 1.01 1.05
38
0.79 0.87 0.94 0.99 1.04
39
0.76 0.84 0.92 0.97 1.02
40
0.72 0.81 0.89 0.95 1.00
41
0.69 0.78 0.87 0.92 0.98
42
0.65 0.74 0.84 0.90 0.95
43
0.61 0.71 0.81 0.87 0.93
44
0.57 0.67 0.78 0.84 0.90
45
0.52 0.63 0.75 0.81 0.87