User`s guide

ACF60-00 – Installation, User’s and Maintenance Manual
16
Ed. 04/2012
ACF60-00 HT, ACF60-00 HT S – COOLING CAPACITY CORRECTION FACTORS
Table 7 ACF60-00 HT, ACF60-00 HT S – Cooling capacity multiplication correctional factors for external air
temperatures and water flow rates different from the nominal values reported in the table.
WATER DELIVERY TEMPERATURE °C
EXTERNAL AIR
TEMPERATURE
°C
5.0 7.0 10.0 12.5 14.0
0
1.02 1.02 1.02 1.02 1.03
2
1.02 1.02 1.02 1.02 1.03
4
1.02 1.02 1.02 1.02 1.03
6
1.02 1.02 1.02 1.02 1.03
8
1.02 1.02 1.02 1.02 1.03
10
1.02 1.02 1.02 1.02 1.03
12
1.02 1.02 1.02 1.02 1.03
14
1.02 1.02 1.02 1.02 1.03
16
1.02 1.02 1.02 1.02 1.03
18
1.02 1.02 1.02 1.02 1.03
20
1.02 1.02 1.02 1.02 1.03
22
1.02 1.02 1.02 1.02 1.03
24
1.02 1.02 1.02 1.02 1.03
26
1.01 1.02 1.02 1.02 1.03
28
1.01 1.02 1.02 1.02 1.03
30
1.01 1.02 1.02 1.02 1.03
32
0.99 1.02 1.02 1.02 1.03
34
0.96 1.01 1.01 1.01 1.02
35
0.94 1.00 1.00 1.01 1.02
36
0.92 0.99 1.00 1.00 1.02
38
0.87 0.97 0.99 0.99 1.01
40
0.82 0.93 0.97 0.98 1.00
42
0.88 0.94 0.97 0.99
44
0.82 0.91 0.95 0.97
46
0.86 0.92 0.95
48
0.80 0.87 0.91
50
0.81 0.86