ACF60-00 TK, ACF60-00 TK S – COOLING CAPACITY CORRECTION FACTORS
Table 5 – ACF60-00 TK, ACF60-00 TK S – Cooling capacity multiplication correctional factors for external air
temperatures and water flow rates different from the nominal values reported in the table.
WATER DELIVERY TEMPERATURE °C
EXTERNAL AIR
TEMPERATURE
°C
3.0 5.0 7.0 9.0
-12
1.18 1.18 1.19 1.20
-10
1.18 1.18 1.18 1.19
-8
1.17 1.17 1.18 1.19
-6
1.16 1.16 1.17 1.18
-4
1.16 1.16 1.16 1.18
-2
1.15 1.15 1.16 1.17
0
1.15 1.15 1.15 1.16
2
1.14 1.14 1.15 1.16
4
1.14 1.14 1.14 1.15
6
1.13 1.13 1.14 1.15
8
1.12 1.13 1.13 1.14
10
1.12 1.12 1.12 1.13
12
1.12 1.12 1.12 1.13
14
1.11 1.11 1.11 1.12
16
1.11 1.11 1.12 1.12
18
1.10 1.10 1.11 1.11
20
1.09 1.09 1.11 1.11
22
1.08 1.08 1.10 1.10
24
1.06 1.06 1.10 1.10
26
1.03 1.05 1.09 1.09
28
0.98 1.02 1.08 1.08
30
0.92 0.99 1.06 1.07
32
0.85 0.95 1.04 1.06
34
0.75 0.90 1.02 1.04
35
0.69 0.87 1.00 1.03
36
— 0.84 0.98 1.02
38
— — 0.94 0.99
40
— — 0.89 0.95
42
—
—
0.83 0.91
44
—
—
— 0.85
45
—
—
—
0.82