ACF60-00, ACF60-00 S – COOLING CAPACITY CORRECTION FACTORS
Table 3 ACF60-00, ACF60-00 S – Cooling capacity multiplication correctional factors for external air
temperatures and water flow rates different from the nominal values reported in the table.
WATER DELIVERY TEMPERATURE °C
EXTERNAL AIR
TEMPERATURE
°C
3.0 5.0 7.0 9.0
0
0.98 0.99 1.01 1.03
5
0.98 0.99 1.01 1.03
10
0.98 0.99 1.01 1.03
15
0.98 0.99 1.01 1.03
20
0.98 0.99 1.01 1.03
25
0.97 0.99 1.01 1.03
30
0.90 0.98 1.01 1.03
35
0.67 0.87
1.00
1.02
40
0.88 0.93
45
0.67 0.78