Technical data

2 Transport and placement
Installation, Use and Maintenance Manual – GA Line ACF Series
17
ACF60-00 ACF60-00 HR ACF60-00 TK ACF60-00 HT ACF60-00 LB
Gas tting
TYPE F
thread " G 3/4
Size
width mm 850
depth mm 1230
height mm 1290
silenced height mm 1540
Weight In operation kg 360 390 380
Note:
(1) As per standard EN12309-2
(2) For ows other than nominal refer to Planning Manual
(3) PCI (G20) 34.02 MJ/m3 (1013 mbar 15 °C)
(4) PCI (G30/G31) 46.34 MJ/kg (1013 mbar 15 °C).
(6) ± 10% according to the power supply voltage and tolerance on electrical motors
consumption
(7) Sound power values detected in compliance with the intensity measurement
methodology set forth by standard EN ISO 9614.
(8) Maximum sound pressure levels in free eld, with directionality factor 2, ob-
tained from the sound power level in compliance with standard EN ISO 9614.
Table 1.2 – PED data
ACF60-00 ACF60-00 HR ACF60-00 TK ACF60-00 HT ACF60-00 LB
PED data
COMPONENTS UNDER
PRESSURE
Generator l 18,6
Leveling chamber l 11,5
Evaporator l 3,7
Cooling volume
transformer
l 4,5
Cooling absorber
solution
l 6,3
Solution pump l 3,3
TEST PRESSURE (IN AIR) bar g 55
MAXIMUM PRESSURE OF THE COOLING CIRCUIT bar g 32
FILLING RATIO
kg of
NH3/l
0.173 0,159 0,177 0,157 0,173
FLUID GROUP
2 TRANSPORT AND PLACEMENT
2.1 WARNINGS
Damage from transport or installation
The manufacturer shall not be liable for any damage
during appliance transport and installation.
On-site inspection
Upon arrival at the site, ensure there is no transport
damage on packing, metal panels or nned coil.
After removing the packing materials, ensure the ap-
pliance is intact and complete.
Packing
Only remove the packing after placing the appliance
on site.
Do not leave parts of the packing within the reach of
children (plastic, polystyrene, nails...) since they are
potentially dangerous.
Weight
The crane and lifting equipment must be suitable for
the load.
Do not stand under suspended loads.
2.2 HANDLING
Handling and lifting
Always handle the appliance in its packing, as delivered by
the factory.
To lift the appliance use straps or slings inserted in the holes
of the base (Figure 2.1p.18).
Use hanging and spacing rods to avoid damaging the outer
panels and nned coil (Figure 2.1p.18).
Comply with safety regulations at the installation site.