Technical data

22
activate FAN ONLY mode;6.
activate HEATING mode;7.
in HEATING mode, close the gas supply line and check that the lockout led on the 8.
reset button "B" lights up after a few seconds (detail "3" - Figure 4.1 29);
now check that when you open teh gas cock and press reset button "B", the lockout 9.
led goes out and the generator starts up again;
If the appliance behaves in any other way than specified in the procedures in Paragraph
4.1 SWITCHING ON AND SWITCHING OFF 29 or exhibits any anomalous behaviour,
this indicates a possible wiring error. Check the connections and if the anomaly persists,
contact your local TAC or Robur Spa Service (tel. +39.035.888.111).
CONTROLLING MULTIPLE APPLIANCES WITH A SINGLE EXTERNAL ENABLE SIGNAL
Terminals "Z9-Z9" enable you to control multiple generators with a single external enable
signal (e.g.: analogue thermostatic programmer, clock, etc.).
There are three possible control options as shown in Figures 3.12 25, 3.13 26 and
3.14 27:
control of multiple appliances with a single programmer and multiple room •
thermostats;
control of multiple appliances with a single programmer and a single room ther-•
mostats (with multiple relays);
control of multiple appliances with a single programmer and a single room ther-•
mostats (with a single relay).
3.5 SETTING THE GAS VALVE
For correct operation of series B15 generators, the gas valve must be set to the values
given in Table 3.5 23. The appliance is shipped with the gas valve already set.
If further adjustment should be necessary, proceed as explained below (see Figure
3.10 23).
The adjustment must be done by professionally qualified personnel. ROBUR S.p.A. has
a network of Assistance Centres which can be contacted via your reseller, area agent, or
by phoning ROBUR S.p.A. Customer Assistance tel. +39.035.888.111.
You will need: the appliance connected to the power/gas supply. Necessary equip-
ment and materials.
Connect a pressure gauge to pressure fitting "B", after having slackened off the seal 1.
screw.
If using a differential gauge, connect gas valve fitting "B" to the gauges + (positive)
terminal.
Turn on the appliance and wait for the flame to reach a steady state (around 2 2.
minutes).
Operation with hatch open: remove its cap with a screwdriver and adjust offset 3.
adjuster screw "A" (you will need a 4 mm allen key) to the nominal value given in
3.5 23.