Technical data
Installation, user and maintenance manual – Series B15 Generators
13
3 INSTALLATION
3.1 GENERAL INSTALLATION INSTRUCTIONS
The installation must be done, as instructed by the manufacturer, by • profession-
ally qualified personnel.
• Professionally qualified personnel is defined as those possessing specific techni-
cal competence in the residential heating equipment sector. Contact ROBUR S.p.A.
Presales (tel. +39.035.888.111) for any further information.
Incorrect installation may cause damage to persons, animals or things, for which •
the manufacturer is not liable.
The installation must be done in accordance with established local and national •
regulations, in particular:
Italian Ministerial Decree of 12 April 1996 containing fire prevention regula-•
tions regarding the design, construction and operation of heating systems
supplied with gas fuel;
Italian Decree n. 412/93 governing the design, installation, operation and •
maintenance of heating systems;
Italian Decree n. 551/99 which introduces certain modifications to D.P.R. n. •
412/93;
Italian Law n. 46/90 and its actuating regulation (D.P.R. 447/91) regarding the •
safety of heating systems;
UNI CIG 7129 governing the installation of appliances supplied with natural •
gas;
Italian Law n. 186 of 1 March 1968 regarding the installation of electrical •
systems.
On the basis of the installation design, set out the gas and electrical supply lines, as well as
the appliance’s supporting brackets. The appliance may be installed horizontally, at an an-
gle or vertically (air flow downwards), using the optional mounting bracket (3.1 → 13).
Figure 3.1
Possible installation positions for series B15 generator.
During the installation, observe the following precautions:
Unpack the appliance, and check it for damage suffered during shipping; each ap-•
pliance is factory tested before shipping; if it is damaged, notify the shipping agent
immediately.
Allow a clearance of at least 300 mm between the back of the appliance and the •
wall for an adequate air supply (see Figure 3.2 → 15).
The optimal recommended height from the ground of the generator’s base is 2.5 •
m (see Figure 3.2 → 15). Do not install the appliance at less than 2.20 m above the
ground.