Technical data
10
2.4 TECHNICAL DATA
Table 2.1 – Technical data.
TECHNICAL CHARACTERISTICS unit of measurement B15
appliance category I
2H
appliance type C13-C33-B23-C63-C53
gas natural (methane) G20
thermal capacity nominal kW 15
thermal power nominal kW 13,8
gas consumption
(1)
natural (G20) m3/h 1,59
efficiency nominal % 92
gas supply pressure natural gas (G20) mbar 20
gas fitting dia. "G 3/4 F
fumes/combustion air fitting dia.
air intake mm 80
fumes outlet mm 80
electrical power
voltage V 230
TYPE single-phase
frequency 50 Hz supply 50
electrical power absorption nominal w 160
fuse - A 3.15
operating temperature
(2)
in room °C 0 ÷35
air flow
(3)
nominal m3/h 1900
thermal differential - k 21
air throw
(4)
residual speed > 1m/s m 12
sound level at 6 m open area dB(A) 40
sound level at 6 m typical installation dB(A) 52
weight - kg 28
Technical data.
Notes:
At 15 °C - 1013 mbar.1.
WARNING: The operating temperature IN THE ROOM is 0 °C/+35 °C; The operating 2.
temperature OF THE APPLIANCE’S COMPONENTS is 0 °C/+60 °C;
At 20 °C - 1013 mbar.3.
Values measured in an open area; in a real installation, the thermal flow may reach 4.
GREATER distances than those given here (depending on the height of the ceiling
and its thermal insulation).