Technical data
7 Installation, use and Maintenance manual - ed. 04/14
SECTION 2 INSTALLATION
This installation section describes the installation of the cooler with standard controls. If other
control such as a thermostat or humidistat is to be used the 5 speed control panel instructions must
be consulted
2.1 - Delivery
The unit is delivered mounted on a pallet
which is used to support the unit during
installation. A protective cardboard cover is,
together with internal polystyrene pads,
banded to the pallet.
This is a fragile item and must be handled
carefully. The maximum stacking height is 2.
Once removed from the pallet take great care
not to damage the drain which protruded from
the bottom of the unit.
2.2 - Installation
The dimensions of the unit are shown in the
diagram opposite.
A minimum of 300mm clearance must be
provided around the unit to enable the side
panels to be removed.
The operating weight of the unit, when full of
water is 92Kg
AD 14
is designed to be supported from a
plain square duct with nominal external
dimensions 645mm x 645mm.
Note that due to the variation in the
moulding of plastics there may be
some variation in these dimensions –
the final duct must be manufactured to
fit the cooler.