- ROBOTIS Dynamixel RX-28 User's Manual
DYNAMIXEL 
RX-28 
Status Packet Result NO ERROR 
Example 20  Lock all addresses except for Address 0x18 ~ Address0x23 for a Dynamixel 
actuator with an ID of 0 
Set Address 0x2F (Lock) to 1. 
Instruction Packet   
  Instruction = WRITE_DATA, Address = 0x2F, DATA = 0x01 
Communication 
->[Dynamixel]:FF FF 00 04 03 2F 01 C8 (LEN:008) 
    <-[Dynamixel]:FF FF 00 02 00 FD (LEN:006) 
Status Packet Result NO ERROR 
  Once locked, the only way to unlock it is to remove the power. 
If an attempt is made to access any locked data, an error is returned. 
->[Dynamixel]:FF FF 00 05 03 30 40 00 87 (LEN:009) 
    <-[Dynamixel]:FF FF 00 02 08 F5 (LEN:006) 
Range Error 
Example 21  Set the minimum power (Punch) to 0x40 for a Dynamixel actuator with an ID of 0 
Instruction Packet   
  Instruction = WRITE_DATA, Address = 0x30, DATA = 0x40, 0x00 
Communication 
->[Dynamixel]:FF FF 00 05 03 30 40 00 87 (LEN:009) 
    <-[Dynamixel]:FF FF 00 02 00 FD (LEN:006) 
Status Packet Result NO ERROR 
30