User Manual
7
554228 Rev. E July 30, 2013
Select Units
Theoperatormaychoosetohaveunitsofmeasure
displayedinpounds,kilograms,ounces,orgrams.
1.UsetheUPorDOWNarrowkeyorselect
TOGGLE UNITStotogglethroughthechoices.
2.
SelectSAVE tochoosethedisplayedunitof
measure.
Set Date and Time
Themachineisprogrammedatthefactoryforthe
localtimezoneanddate.Usethekeypadand
arrowkeystorevisethatinformation.
1.Usethekeypadtoenterthedateandtime.
Press“2”forAM;press“7”forPM.
2.SelectSAVE toacceptthedateandtime.
Adjust Tank Fill Default
Theoperatormayeitheraccepttheunit’spre-set
defaultweightof15lbs.ofrefrigerantstoredinthe
internalstoragevessel(ISV),orchangetheamount
toaccommodatetheapplication.Theunitdisplays
15.00LBS.
ENTERTHEAMOUNTOFREFRIGERANTTHAT
THETANKFILLFUNCTIONSHOULDMAINTAIN
INTHEINTERNALSTORAGEVESSEL.
MAX=17.00LBMIN=04.00LB
SELECTSAVETOACCEPTOREXITTOABORT
1.
SelectSAVEtoacceptthedefaultamount,oruse
thekeypadtoenteranamountandselectSAVE.
Maintain Vacuum Pump
Note: Service hoses are shipped in the accessory kit.
Theunitdisplays
INSTALLSERVICEHOSESONTOBULKHEADS
ANDSTORAGEPORTS.
ADD5OZOFNEWOILTOVACUUMPUMP.
PRESSNEXTTOCONTINUEOREXITTO
ABORT.
1.Connecttheservicehosesfromthebulkhead
ttings(locatedonthesideoftheunit)tothe
storageports.SeeFigure4.Connectthered
hosetothettinglabeledHIGH;connectthe
bluehosetothettinglabeledLOW.
Figure 4
Side View
Hose
Bulkheads
Hose Storage
Ports
Oil Fill Port
Vacuum Pump
Sight
Glass
Setup
CAUTION: R-134a systems have special
ttings (per SAE specications) to avoid
cross-contamination with other systems.
DO NOT adapt your unit for a different
refrigerant — system failure will result.