Setup
Fill the Internal Storage Vessel (ISV)
1.
PressSTART / YES, and the unit automatically
runsa5-minutevacuumtoclearallinternalair.
Note: The “burping” noise heard during this
process indicates air is being purged from the
system—this is normal.
2.Afterthevacuumpumpshutsoff,connect
thellhosetotheliquidconnectoronafull
sourcetank.
3.Openthesourcetankvalve.
4.Installthesourcetank,andsecureittothe
unit(usingthetankstrap)insuchaway
thatliquidrefrigerantissuppliedtothe
connection.
5.PressSTART / YEStobeginllingthe
internalstoragevessel.Addatleast8lbs.
(3.6kg)ofrefrigeranttoensureenough
refrigerantisavailableforcharging.
Thisprocesstakes15–20minutes.Theunit
stopswhenasufcientamountofrefrigerant
hasbeentransferredtotheinternaltank,or
whenthesourcetankisempty.
PressSTOP / NOtopause.PressSTOP /
NOagaintoexit,orSTART / YEStoresume.
6.Whenthellprocessiscomplete,press
STOP / NOtoexit.Theunitisreadyfor
operation.
Note: There is no need to calibrate the scale; it
is calibrated at the factory.