User Manual
18
5.ThedisplayreadsPLEASE REPLACE FILTER.
Openthereardooroftheunitandunscrewtheold
lter.SeeFigure13.
6.
Lookatthenewlter—verifybotho-ringsare
lubricatedandcorrectlylocatedinthegrooves.See
Figure14.Threadthenewlterintoplace.Press
START / YES.
Note: If the display shows SERIALNUMBERERROR,
the serial number is invalid or the lter-drier has
already been used in this unit.
7.Closethedoor.PressSTOP / NOtoexit.Thelter-
drierreplacementisnowcomplete.
Replace the Filter-Drier contd.
Filter-
Drier
Rear View
(without shroud)
Figure 13
Scale Calibration Check
Thecalibrationcheckisusedtoensurethattheunit’s
internalscaleisalwayscalibrated.Duringthistest,use
onlythecalibrationweightthatisprovidedwiththeunit.
1.PressMenu.
2.UsethearrowkeystoscrolltoCALIBRATION
CHECK.
3. Refer to Figure 15, and verify the magnet on the
bottomoftheunitisclean.PressSTART / YES.
4.Thedisplayreads
ATTACHTHEWEIGHTTOTHEBOTTOMOFTHE
MACHINE
PRESS START TO CONTINUE
5. Attach the weight provided to the magnet on the
bottomoftheunit.PressSTART / YES.
• IfthedisplayshowsCALIBRATIONAPPROVED,the
scaleisincalibration.Pressanykeytoexit.
• IfthedisplayshowsCALIBRATIONREJECT,the
scaleisoutofcalibration.Callyourlocalservice
centerforassistance.
• IfthedisplayshowsCALIBRATIONERROR1,verify
thecalibrationweightiscorrectlyattachedtothe
magnet,andverifythemagnetiscleanwithnothing
attachedtoit.Ifthatdoesnotcorrecttheproblem,
callyourlocalservicecenterforassistance.
Magnet
Figure 15
O-rings
Figure 14