Service Solution Manual

24
© 1999 Robinair, SPX Corporation
RECOVER
Verify that the service hoses are connected and the coupler valves are
open.
The system must have at least 25 psi of pressure for correct operation of
the refrigerant ID.
SET-UP MENU (Use the UP/DOWN arrows to highlight selections)
Language
- Press TOGGLE SELECTION to select English, Spanish, or French.
- Press the MAIN key to exit.
Select Units (Selects the units of measure in English or Metric)
- Press TOGGLE SELECTION.
- Press the MAIN key to exit.
Clock Adjust (Adjusts the date and time)
- Press the ENTER key.
- Use the UP/DOWN arrows to change the date and time.
Change Elevation (Sets the altitude above sea level for your location)
- Enter the numeric value.
Calibrate Pressure (Calibrates high and low side pressure transducers)
- Disconnect service hoses and press the ENTER key.
Anemometer (Enables and calibrates optional anemometer)
- Instruction detail included with the anemometer.
Manual Oil Drain (Allows user to manually drain any oil from the
342000)
- Press the ENTER key.
- Press the EXIT key.
Hose Length
- Allows accurate charging with varying lengths of hose.
Refrigerant Management
- Displays details on refrigerant usage.
Operating Instructions