Owner manual
Model 17800B/17801B Recovery/Recycling/Recharging Unit
27
ENGLISH
7. If the scale does not read the weight accurately, recalibrate the scale and
UL circuit using the following instructions. If the scale does not respond to
testing, verify the scale cable is plugged into the main circuit board.
8. Press SHIFT/RESET to exit this mode
CALIBRATING THE SCALE
NOTE: ThescaleassemblyandULcircuitMUSTbecalibratedwheninstalling
areplacementscaleassemblyorcircuitboard.Toensurecontinuedcharging
accuracy,periodicallyconrmthechecklistbelow.
1. Remove all weight from the scale platform.
2. Turn on the MAIN POWER switch.
NOTE: Iftheunitisjustbeingturnedon,thescreenwilldefaulttodisplaythe
selectedrefrigeranttype.
3. Press SHIFT/RESET and ENTER until “PROGRAM” displays.
4. When the “PROGRAM” message displays, press SHIFT/ RESET at the
same time. The “FUNC” message displays.
5. Press 9. The display is blank.
6. Press RECOVER and ENTER at the same time.
7. The DATE message ashes, then “0.00” displays. Enter the current month and
year. For example, if the unit is being calibrated on November 8th, 1998, enter
1,1,9,8 and then press ENTER.
8. The “CAL” message will ash, then the “ZERO” message displays.
9. Verify nothing is on or touching the scale platform, then press ENTER.
10. The “CAL” message will ash, then the “A1” message displays.
11. Place a certied weight (between 20 and 70 lbs.) in the center of the scale
platform. Enter the weight from the display. For example, to record 20 lbs.
on the scale, press “2,0,0,0” on the keypad, then press ENTER. The display
returns to the vacuum mode.
Maintenance Procedures