This overview is designed as a quick reference when using your unit. Read and
follow all warnings in the operating manual.
RECOVERY OVERVIEW
1. Connect the high- and low-side hoses to the A/C-R system.
2. Check the manifold gauges. There must be pressure to recover refrigerant.
3. Verify both the high- and low-side valves on the control panel are open. Also
verify both valves on the tank are open.
4. Plug the unit into a correct voltage outlet, then turn on the MAIN POWER
switch.
5. Press RECOVER:
If there is pressure in the unit, the self-clearing process starts.
If there is no internal pressure, refrigerant recovery begins.
The unit then shows “RECOVER AUTOMATIC” and the weight of
refrigerant being recovered into the tank.
6. Once the recovery and/or self-clearing procedure is complete, the compressor
shuts off automatically. The display will ash “CPL” and the weight of
refrigerant recovered.
7. If the A/C-R system pressure rises above zero, press HOLD/CONT to
recover the remaining refrigerant.
8. The display also shows “OIL (OUNCES).” This is a reminder to drain the
system oil separator into a suitable container by opening the ball valve on the
side of the unit.
You must replace any oil lost from the A/C-R system during recovery with
new oil. Dispose of waste oil in an appropriate manner.