Troubleshooting
RECYCLING OPERATION
Compressor does not start or stops prematurely
Problem: Power cord is not plugged in or there is no power at plug
Solution: Check circuit for power
Problem: Tank valves are closed
Solution: Open both valves and be sure hoses are properly
connected to the tank
Problem: “CH-F” message on digital display
Solution: Remove and replace the filter-drier (see Replacing the Filter-Drier),
and be sure to pull a vacuum before continuing
Refrigerant does not flow
Problem: Refrigerant supply empty or low
Solution: Add refrigerant to the tank
Problem: Tank valves are closed
Solution: Open both valves and be sure hoses are properly
connected to the tank and the unit
RECHARGING OPERATION
No power when MAIN POWER switch is on — no display showing
Problem: Power cord is not plugged in or there is no power at plug
Solution: Check circuit for power
Problem: The “CHECK REFRIGERANT” message is displayed
Solution: There is less than 6 pounds of refrigerant in the tank; add refrigerant to
the tank
Audible tone sounds during refrigerant transfer
Problem: Transfer stopped or too slow
Solution: Close the high side valve, then start the A/C-R system and pull the
remaining refrigerant into the system
Problem: Refrigerant supply is low or empty
Solution: Add refrigerant to the tank or change tanks