Specifications

Model 17800B Recovery/Recycling/Recharging Unit
21
Weight Example *
* The display shows the weight of
refrigerant added to the tank.
(Adding Refirgerant to the Tank continued)
This process takes about 45 minutes. You can interrupt it at any time by pressing
HOLD/CONT once. Press HOLD/CONT again to resume
operation, or press SHIFT/RESET to end the process. The transfer of new
refrigerant is limited by weight to leave space (about 6 pounds of refrigerant) in the
unit tank for recovery purposes.
8. When using R-12, close the supply valve on the source tank (when
using a disposable tank, turn it right side up first). Carefully disconnect the 96 inch
(244-cm) blue low-side hose from the 6-inch (15.2-cm) yellow adapter, and
then remove the yellow adapter from the source tank.
When using R-134a, close the supply valve on the source tank, (when using
a disposable tank, turn it right side up first). Carefully disconnect the 96 inch
(244-cm) blue low-side hose from the low-side connector port adapter and
then remove the adapter from the source tank.
9. Press RECOVER. The hose will be pulled into a partial vacuum and the unit
will turn off automatically. If the hose is partially clear, the unit will display
"CH-P". Press HOLD/CONT to finish clearing the hose. Close the low-side
manifold valve.
10. Connect the 96-inch (244-cm) red high-side hose to the unit's high-side port.
You can also attach an oil injector to the unit's low-side port. Oil injectors will
not connect to the wrong ports. The R-12 oil injector has a ¼ inch flare
connector; the R-134a oil injector has a ½ Acme connector.
Any non-condensable gases in the tank can be removed during the recycling
sequence. Your unit is now ready for use.
Operating Instructions
IMPORTANT!
Be sure to close
both tank valves
when the unit is
not in use. In-
spect the unit pe-
riodically for
leaks. The manu-
facturer of the re-
covery/recycling
unit does not re-
imburse for lost
refrigerant.