Operating Instructions
A/C-R SYSTEM EVACUATION
WARNING!
Always wear safety goggles when working with refrigerant. Use only autho-
rized refillable refrigerant tanks. Disconnect hoses with extreme caution!
All hoses may contain refrigerant under pressure. Read and follow all
warnings at the beginning of this manual before operating the unit.
1. Be sure the high and low side hoses are connected to the A/C-R
system and that the high and low side valves are open.
2. Press SHIFT/RESET to toggle the display to show “PROGRAM VACUUM
MINUTES 15.00.” Fifteen minutes is the default time for evacuation. To change
the time, press the appropriate keys to display the desired time. Then press EN-
TER.
The longest time that can be programmed is 98.99 (98 minutes and 99 sec-
onds).
3. Press VACUUM to start evacuation. The display counts down the time remaining.
If the message “U-HI” appears, you have 25 psi or greater of pressure at the inlet.
You must recover that pressure to continue. If necessary, press RECOVER.
4. When the programmed time has expired, the vacuum pump will automatically shut
off and the display will show “CPL.” Press any key to exit vacuum mode.
To run the vacuum pump continuously, program the time to “99.00,” press EN-
TER, then press VACUUM. The pump will start and the display will show “CON
AUTOMATIC VACUUM.” To turn the vacuum pump off, press HOLD/CONT.