Specifications
© 2001 Robinair, SPX Corporation
14
Operating Instructions
Important!
Before changing
refrigerant types,
be sure the red
high side and blue
low side hoses are
disconnected from
the A/C system.
CHANGING REFRIGERANT TYPES
1. Be sure the red high side and blue low side hoses are disconnected from the A/C
system, then open the manifold and tank valves.
2. Press and release SHIFT/RESET until the “Clr” message appears.
3. Press HOLD/CONT to start the system oil separator clearing process.
During the system oil separator clearing process, the compressor is activated and
the “OIL” message displays. The compressor will stop while the unit equalizes
pressure and the “OIL” message will continue to display. When the unit reaches the
correct pressure, the display alternately flashes the messages “OIL” and “drn.”
Open the system oil drain valve to drain the oil. After all oil has drained, close the
oil drain valve. The message changes to “Cont.” Press any key to complete the oil
separator clearing process. When compressor stops again, the message changes to
"CL-c."
First!
Perform
"RECOVERY
PROCE-
DURES"
before starting
"CHANGING
REFRIGER-
ANT TYPES".
AUTOMATIC
Diagram of Unit’s Components — External View
High Side Port
Lockout Door
Blue Liquid Hose
Red Vapor Hose
Yellow Air Purge Hose
Air Purge
Fitting
50 lb. (23 kg)
Unit Tank
Scale Assembly
Low Side Port
Tank Vapor Valve
Tank Liquid Valve