Specifications

Model 17800B Recovery/Recycling/Recharging Unit
11
Set Up Instructions
Before using a new tank, you must purge its nitrogen charge and pull it into a vacuum.
The 50 lb (23kg) unit tank must be filled with refrigerant before the unit is ready for use.
Tank Fill
17. Connect the 96" Blue low side hose to the fitting on the source tank. If using R-
134a you may need the 1/2" acme to low side adapter included in the accessory
kit.
18. Press SHIFT/RESET and ENTER at the same time, then press 2. The unit will
begin transfering refrigerant from the source tank to the unit tank.
19. The unit will fill the recovery tank up to 30 lbs of refrigerant and automatically stop.
The display will flash "CPL" when the process is complete.
20. To discontinue tank fill at any time press HOLD/CONT.
WARNING!
Always wear safety goggles when working with refrigerant. Use only autho-
rized refillable refrigerant tanks. Disconnect hoses with extreme caution!
All hoses may contain refrigerant under pressure. Read and follow all
warnings at the beginning of this manual before operating the unit.