User Guide
INSTALLER SETUP MENU
13
Tech Settings LCD Will Show Adjustment Options Default
Compressor
Short Cycle
Delay
The compressor short cycle
delay setting will not allow the
compressor to be turned on for 5
minutes after it was last turned off
in order to protect the compressor.
Next step
Prev step
The compressor short cycle
delay setting can be removed
by selecting OFF.
ON
Cooling
Differential
The cooling differential is factory
preset at 0.5°. This means that
whenever the room temperature
heats by 0.5° full degree from the
temperature setting, the cooling
system will turn on. If the cooling
system turns on too often, increase
the temperature differential.
Next step
Prev step
The cooling differential setting is
adjustable from 0.2°F to 2°F.
0.5
Heating
Differential
The heating differential is factory
preset at 0.4°. This means that
whenever the room temperature
cools by 0.4° from the temperature
setting, the heating system will
turn on. If the heating system
turns on too often, increase the
temperature differential.
Next step
Prev step
The heating differential setting is
adjustable from 0.2°F to 2°F.
0.4
Settings Display Adjustment Options Default