User Guide

Filter
Change
Reminder
This setting will ash FILT in the
display after the elapsed run time
to remind the user to change the
lter. The OFF setting will disable
this feature.
Next step
Prev step
The filter change reminder
can be adjusted from OFF
to 2000 hours in 50 hour
increments. Press the second
button from the top left side of
the thermostat to display the
current filter elapsed runtime.
OFF
Room
Temperature
Calibration
This setting allows the installer to
change the calibration of the room
temperature display so that, for
example, the thermostat would
read 72°F instead of 70°F.
Next step
Prev step
The room temperature display
can be adjusted to read up to
3° above or below the factory
calibrated temperature.
0
Minimum
Compressor
On-Time
The installer can select the
minimum run time for the
compressor to help protect the
compressor from short-cycling.
Next step
Prev step
The minimum compressor run
time can be adjusted from OFF
to 3, 4, or 5 minutes. If 3, 4, or
5 is selected, the compressor
will run for at least the
selected time before turning off
(although the fan may continue
to run for a short time).
OFF
Settings Display Adjustment Options Default
INSTALLER SETUP MENU
12