Specifications

Timers
Delay on Break Timers (Anti-Short Cycle Protection)
APPLICATIONS TIMING DIAGRAM
“Anti-short cycle” “ON delay on break”
Helps to protect air conditioning, refrigeration and heat pump equipment from damage which may be
caused by the rapid short cycling of compressors.
MODE OF OPERATION
Upon application of power, the load is energized. When the thermostat or other switch opens or there is a
loss of power, the load is de-energized and the delay period begins. The compressor will not start again
during the delay period. Restart occurs after the delay period has elapsed.
Delay on Break Timers
ICM Control Features and Applications Specifications Replaces
ICM200, 200F, 201, 201F
Higher 1.5 amp power rating
Compressor lockout/anti-short cycle timer
Helps to protect compressors from damage caused by rapid
short cycling
Simple, 2-wire hookup
SERIES: ICM200, 200F: 3-minute delay
ICM201, 201F: 5-minute delay
”F” suffix denotes 6” wire leads
Voltage: 18-30 VAC
1.5 amps
15 amp inrush
Frequency: 50-60 Hz
Fixed time delays: 3 or 5-minutes
Voltage drop:
• 3.5 V typical
• 4.5 V maximum @ 1.5 amps
Holding current minimum: 40 mA
Dimensions: 2” x 2”
ICM200
A-1: EAC-501-180-W
Diversified: AC-100-3
Supco: TD733 (18-30 VAC)
ICM200F
A-1: EAC-500
Supco: TD733W (18-30 VAC)
ICM201
A-1: EAC-500,
EAC-501-300-W
Diversified: ASC-500-5
Mars: 32390
Supco: TD735 (18-30 VAC)
ICM201F
A-1: EAC-500,
EAC-501-300-W
Diversified: AC-505-5
Mars: 32005, 32505
Supco: TD735W (18-30 VAC)
ICM203, 203F
Universal voltage operation
Higher 1.5 amp power rating
Compressor lockout/anti-short cycle timer
Helps to protect compressors from damage caused by rapid
short cycling
Simple, 2-wire hookup
”F” suffix denotes 6” wire leads
Voltage: 18-240 VAC
1.5 amps
15 amp inrush
Frequency: 50-60 Hz
Knob-adjustable delays: .03-10 mins.
(1.8-600 sec.)
Voltage drop:
3.5 V typical
4.5 V maximum @ 1.5 amps
Holding current minimum: 40 mA
Dimensions: 2” x 2”
ICM203
A-1: EAC-501-ADJ
Diversified: AC-503
Mars: 32001, 32387, 32392
Robertshaw: 3310-072
Supco: TD72, TD73
Wagner/DiversiTech: ADB-1
ICM203F
Supco: TD73W
Wagner/DiversiTech: ADB-2
ICM204, 205, 206
Brownout protection
UL 873 recognition as compressor controller
Helps prevent scroll compressor reversal
Fast response time: 16 ms
Compressor lockout/anti-short cycle timer
Prevents low voltage starts
Eliminates relay chatter due to thermostat bounce or
tampering
Works with anticipator-type thermostats
Patented: U.S. Patent No. 4,991,049
SERIES: ICM204: 3-minute delay
ICM205: 5-minute delay
ICM206: 3-10 minute delay
Voltage: 18-30 VAC
1.5 amps
15 amp inrush
Frequency: 50-60 Hz
Adjustable time delays:
3 or 5-minute fixed or 10-minute
adjustable time delay
Holding current minimum: 40 mA
Dimensions: 2” x 2”
ICM204
A-1: EAC-426-180
Diversified: AC-100-3
Mars: 32381
Robertshaw: 3310-183
Supco: TL243
ICM205
A-1: EAC-426-300
Diversified: AC-100-5
Mars: 32382
Robertshaw: 3310-305
Supco: TL245
ICM206
A-1: EAC-426-ADJ
Supco: TD74
315.233.5266
Phone
All features and specifications subject to change without notice.
Customer Service Fax
315.233.5282
Application Assistance
800.365.5525
Visit www.icmcontrols.com to find all
of our latest products, sell sheets and wiring diagrams