Specifications
Timers
Delay on Break Timers (Anti-Short Cycle Protection)
APPLICATIONS TIMING DIAGRAM
“Anti-short cycle” “ON delay on break”
Helps to protect air conditioning, refrigeration and heat pump equipment from damage which may be
caused by the rapid short cycling of compressors.
MODE OF OPERATION
Upon application of power, the load is energized. When the thermostat or other switch opens or there is a
loss of power, the load is de-energized and the delay period begins. The compressor will not start again
during the delay period. Restart occurs after the delay period has elapsed.
Delay on Break Timers
ICM Control Features and Applications Specifications Replaces
ICM200, 200F, 201, 201F
• Higher 1.5 amp power rating
• Compressor lockout/anti-short cycle timer
• Helps to protect compressors from damage caused by rapid
short cycling
• Simple, 2-wire hookup
• SERIES: ICM200, 200F: 3-minute delay
ICM201, 201F: 5-minute delay
• ”F” suffix denotes 6” wire leads
• Voltage: 18-30 VAC
• 1.5 amps
• 15 amp inrush
• Frequency: 50-60 Hz
• Fixed time delays: 3 or 5-minutes
• Voltage drop:
• 3.5 V typical
• 4.5 V maximum @ 1.5 amps
• Holding current minimum: 40 mA
• Dimensions: 2” x 2”
ICM200
A-1: EAC-501-180-W
Diversified: AC-100-3
Supco: TD733 (18-30 VAC)
ICM200F
A-1: EAC-500
• Supco: TD733W (18-30 VAC)
ICM201
• A-1: EAC-500,
EAC-501-300-W
• Diversified: ASC-500-5
• Mars: 32390
• Supco: TD735 (18-30 VAC)
ICM201F
• A-1: EAC-500,
EAC-501-300-W
• Diversified: AC-505-5
• Mars: 32005, 32505
• Supco: TD735W (18-30 VAC)
ICM203, 203F
• Universal voltage operation
• Higher 1.5 amp power rating
• Compressor lockout/anti-short cycle timer
• Helps to protect compressors from damage caused by rapid
short cycling
• Simple, 2-wire hookup
• ”F” suffix denotes 6” wire leads
• Voltage: 18-240 VAC
• 1.5 amps
• 15 amp inrush
• Frequency: 50-60 Hz
• Knob-adjustable delays: .03-10 mins.
(1.8-600 sec.)
• Voltage drop:
• 3.5 V typical
• 4.5 V maximum @ 1.5 amps
• Holding current minimum: 40 mA
• Dimensions: 2” x 2”
ICM203
• A-1: EAC-501-ADJ
• Diversified: AC-503
• Mars: 32001, 32387, 32392
• Robertshaw: 3310-072
• Supco: TD72, TD73
• Wagner/DiversiTech: ADB-1
ICM203F
• Supco: TD73W
• Wagner/DiversiTech: ADB-2
ICM204, 205, 206
• Brownout protection
• UL 873 recognition as compressor controller
• Helps prevent scroll compressor reversal
• Fast response time: 16 ms
• Compressor lockout/anti-short cycle timer
• Prevents low voltage starts
• Eliminates relay chatter due to thermostat bounce or
tampering
• Works with anticipator-type thermostats
• Patented: U.S. Patent No. 4,991,049
• SERIES: ICM204: 3-minute delay
ICM205: 5-minute delay
ICM206: 3-10 minute delay
• Voltage: 18-30 VAC
• 1.5 amps
• 15 amp inrush
• Frequency: 50-60 Hz
• Adjustable time delays:
• 3 or 5-minute fixed or 10-minute
adjustable time delay
• Holding current minimum: 40 mA
• Dimensions: 2” x 2”
ICM204
• A-1: EAC-426-180
• Diversified: AC-100-3
• Mars: 32381
• Robertshaw: 3310-183
• Supco: TL243
ICM205
• A-1: EAC-426-300
• Diversified: AC-100-5
• Mars: 32382
• Robertshaw: 3310-305
• Supco: TL245
ICM206
• A-1: EAC-426-ADJ
• Supco: TD74
315.233.5266
Phone
All features and specifications subject to change without notice.
Customer Service Fax
315.233.5282
Application Assistance
800.365.5525
Visit www.icmcontrols.com to find all
of our latest products, sell sheets and wiring diagrams
9