Specifications

Fan Coil Thermostats
ICM Control Features and Applications Specifications Terminations
SC700LV/SC700V
• 4 pipe heat/cool
3 speed fan
Auto changeover
24 VAC (SC700LV) and 120-240 VAC (SC700V) versions available
Remote room temperature sensor (Optional: Order ACC-RT103)
Horizontal model available
UL Listed
Temperature Control Ranges:
• 45°F to 90°F, Accuracy:
±
1°F
• 7°C to 32°C, Accuracy:
±
.5°C
System Configurations:
• Fan coil thermostat, 4 pipe; 3 speed fan
N/A
SC710LV/SC710V
• 4 pipe heat/cool
3 speed fan
Manual changeover
24 VAC (SC710LV) and 120-240 VAC (SC710V) versions available
Remote room temperature sensor (Optional: Order ACC-RT103)
Horizontal model available
UL Listed
Temperature Control Ranges:
• 45°F to 90°F, Accuracy:
±
1°F
• 7°C to 32°C, Accuracy:
±
.5°C
System Configurations:
• Fan coil thermostat, 4 pipe; 3 speed fan
N/A
SC900V
2 or 4 pipe • 3 speed fan
Pipe sensor for seasonal
changeover
24 VAC and 120-240 VAC
versions available
Manual or auto changeover
Selectable °F or °C
Occupancy sensing compatible
Valve purge timer
Remote room temperature sensor
(Optional: Order ACC-RT103)
Large backlit display
Icons for fan and outputs
Permanent memory
Key pad lockout function
Maximum heat/minimum cool set
point limits
Soft touch controls
Temperature Control Ranges:
• 45°F to 90°F, Accuracy:
±
1°F
• 7°C to 32°C, Accuracy:
±
.5°C
System Configurations:
• Fan coil thermostat
• 2 or 4 pipe; 3 speed fan
L, N, W/Y, Y/A, GL,
GM, GH, RS, SC,
SB, PS
SimpleComfort® Fan Coil Thermostats
When it comes to freezing cold temperatures, you can relax knowing that ICM’s Frost Sentry™ is on guard. These
low-cost thermostats are perfect for areas where protection from extreme cold is essential. Its special foam
backing improves accuracy by providing separation from the wall at installation, while sealing up any unsightly
wiring holes. This insulated backing helps eliminate the risk of “wall effect” (wall temperature causing false
temperature readings). Ideal for storage areas, garages, workshops, crawl spaces and other critical areas.
Frost Sentry
TM
Garage Thermostats
Frost Sentry
TM
Garage Thermostats
ICM Control Features and Applications Specifications Terminations
FS40
Easy, two-wire installation
Fixed setpoint at 40°F
Special foam backing
improves accuracy; helps
eliminate “wall effect”
Sleek, rugged design
Compatible with most standard
electric heating units
Ideal for storage areas, garages,
workshops and crawl spaces
Input: 18-30 VAC
Output: 2 amps max.
Temperature setpoint: Fixed 40°F
Accuracy: ±5°F
R, W, G
FS1500L
Controls single stage heating
systems
Millivolt, hydronic (water or
steam) system, gas and
electric systems
Battery operated
Backlit display
Mercury-free, environmentally safe
Remote sensor compatible
(ACC-RT104)
Perfect for use with unit heaters
Electrical Rating:
24 VAC (18-30 VAC)
1 amp maximum per terminal
2 amp maximum total load
Easy access terminal block
Temperature control ranges:
35°F to 75°F, Accuracy: ±1°F
R, W, G, S1, S2
FS1500VL
Controls single stage heating
systems
Millivolt, hydronic (water or
steam) system, gas and
electric systems
Battery operated
Backlit display
Mercury-free, environmentally safe
Remote sensor compatible
(ACC-RT104)
Vertical design for easy J-box
installation
Perfect for use with unit heaters
Electrical Rating:
24 VAC (18-30 VAC)
1 amp maximum per terminal
2 amp maximum total load
Easy access terminal block
Temperature control ranges:
35°F to 75°F, Accuracy: ±1°F
R, W, G, S1, S2
315.233.5266
Phone
All features and specifications subject to change without notice.
Customer Service Fax
315.233.5282
Application Assistance
800.365.5525
Visit www.icmcontrols.com to find all
of our latest products, sell sheets and wiring diagrams
48