ICM lead lag controls offer true, dual-stage control to balance the operating run time between two redundant
units. They feature built-in short cycle protection and status LED lights for at a glance diagnostics. Ideal for use in
conjunction with telephone relay hubs/substations and/or remote, unmanned computer stations.
Head Pressure/Accessories
ICM Control Features and Applications Specifications Replaces
ACC-OE-03 (Outdoor Enclosure)
Rugged steel construction
Easy to mount
Helps to protect controls from harsh environmental conditions
such as temperature, shock, humidity and vibration
Ideal for use with ICM head pressure controls
NEMA 3R rated
Dimensions: 4.25” x 6.25” x 6.25”
N/A
ICM379 Probe
Probe for use with ICM325HN, ICM326HN, ICM327HN and
ICM330/ICM332/ICM333 head pressure controls with optional
heat pump bypass feature
Length: 6’ - 7”
70°F to 100°F (21°C to 38°C)
N/A
ICM380
Optional pressure transducer for ICM330/ICM332/ICM333
single phase head pressure controls
Length: 72”
0-500 psi
1/4” SAE female flare with Schraeder
deflator
N/A
Lead-Lag Controls
Reliable Long Life Switching
ICM Control Features and Applications Specifications Replaces
ICM600
True dual stage control
Built in thermostat with:
• Adjustable setpoint
• Adjustable deadband
• Adjustable sequencer
Regulates 1 or 2 heating/
cooling systems
Compact housing
Safety system halon contacts
Memory on power loss
Accelerated test mode
Isolated inputs
Isolated solid state outputs
Built in anti-short cycle
delays
Status LEDs
Advance state switch
Ideal for refrigeration
applications, communication
substations, water treatment
plants anywhere redundant
systems are used
Voltage: 18-30 VAC
Frequency: 50-60 Hz
Maximum amps: 2 amps
Power consumption: watts maximum
Adjustable thermostat features:
Set point: 55°F to 90°F (adjustable)
Deadband: 2°F to 20° (adjustable)
Sequencer: 1-28 days (adjustable)
Dimensions: 4.25” x 8.5” x 2”
N/A
ICM602
Low cost, open board lead lag control
Regulates two devices
Reliable, long life switching
Status LEDs
Ideal for refrigeration applications
Voltage: 18-30 VAC (24 VAC)
Frequency: 50-60 Hz
Maximum amps: 2 amps
Power consumption: 2 watts maximum