Specifications

Condensation Controls
ICM Control Features and Applications Specifications Replaces
ICM340
Low cost condensation control used to prevent
overflowing of an evaporator drain pan
Two sensors for water detection
Adjustable delay before break time to prevent
nuisance trips
Optional overflow LED kit
Voltage: 18-30 VAC
Output:
• 24 VAC to thermostat/cooling control
• 24 VAC to optional overflow LED
Output rating: 2 amps
Delay before trip: 1-3 minutes
Operating frequency: 50-60 Hz
Maximum operating/storage relative humidity:
• 95% non-condensing
Storage temperature: -40°C to +85°C
Quick connects: (1/4 inch) for easy hookup
Provides: Maximum protection against moisture and
allows use in extreme environmental conditions
Water Guard:
401475
ICM342
Low cost condensation sensing control with an
integral delay on make timer
Condensation sensing for overflow protection
Alarm output during lockout
Custom delay on make available (fixed or adjustable)
Conformal coating for moisture protection
Voltage: 18-30 VAC
Frequency: 50-60 Hz
Output:
Type: Relay
N.O.: 10 amps @ 120 VAC
N.C.: 10 amps @ 120 VAC
Time delays: Delay on make: Custom delay available, fixed
or adjustable
Dimensions: 2.75” x 3.25”
N/A
ICM345
Low cost condensation sensing control with anti-
short cycle delay and audible/visual condensation
alarm
Condensation sensing for overflow protection
Audible and visual alarm when condensation is
detected
ASC protection for compressor
Works in conjunction with any thermostat or existing
condensation control
Elegant design
Voltage: 18-30 VAC
Frequency: 50-60 Hz
Output:
Type: Relay
N.O.: 1 amp @ 30 VAC
Audible: Buzzer
Visual: LED Indicator
Time delays: Anti-short cycle: 5-minutes fixed
Dimensions: 4 1/2” x 2 3/4” x 7/8”
N/A
ACH55
Optional overflow alarm LED kit
For use with ICM340 or ICM342
6 ft. cable length
N/A
Prevent Overflowing of an Evaporator Condensation Pan
APPLICATION
ICM’s condensate control systems protect your cooling and refrigeration equipment by detecting and preventing overflows in the evaporator condensation pan due to slow
and/or blocked drains or pump failure. These reliable, low cost controls come with fixed or adjustable delays to eliminate nuisance trips and lockouts. Use in conjunction with
our audible alarm to quickly alert you to an ensuing condensate problem.
ICM340 Wiring Diagrams
Wiring Diagram Breaking “R” Wire Wiring Diagram Breaking “Y” Wire
Wiring Diagram ICM340 with ICM345 Alarm Application
Sensors can be clipped to or pressed
onto side, adhered to bottom of pan
or inserted into drain pipe.
315.233.5266
Phone
All features and specifications subject to change without notice.
Customer Service Fax
315.233.5282
Application Assistance
800.365.5525
Visit www.icmcontrols.com to find all
of our latest products, sell sheets and wiring diagrams
33