Specifications
Gas Ignition Controls
ICM293
• Intermittent Pilot Gas Ignition Control Module
• For use with intermittent pilot boilers, furnaces
and other heating appliances
• Microprocessor-based
• Monitors timing, trial for ignition, flame sensing
and lockout
• Remote flame sensing
• 100% lockout safety feature
• Compatible with LP or Natural Gas
• Status LED for fault codes to aid in
troubleshooting
• Control Voltage: Line 24 VAC (18-30 VAC) 50/60 Hz
• Anticipator Setting: 0.2A plus valve load @ 24 VAC
• Prepurge: 15 seconds
• Trial for Ignition: 85 seconds
• Lockout: 60 minutes
• Flame Failure Response Time: 0.5 seconds
• Status LED: See product label for error codes
• Operating Temperature:
– Min. ambient temperature rating is -40°F (-40°C)
– Max. ambient rating when used with 2.0A main valve
is 165°F (74°C)
• Relative Humidity: 0% to 95% non-condensing
• Lennox:
30W33 ignition control
• Robertshaw:
735L (18G91) or 745
(95H04) ignition controls
• Johnson Controls:
G776 (63K2401, 41K8701,
69J3601) ignition controls
ICM294
• Intermittent Pilot Gas Ignition Control Module
• For use with intermittent pilot boilers, furnaces
and other heating appliances
• Microprocessor-based
• Monitors timing, trial for ignition, rollout switch
flame sensing and lockout
• Remote flame sensing
• 100% lockout safety feature
• Compatible with LP or Natural Gas
• Control Voltage: Line 24 VAC (18-30 VAC) 50/60 Hz
• Anticipator Setting: 0.2A plus valve load @ 24 VAC
• Prepurge: None
• Trial for Ignition: 85 seconds
• Flame Failure Response Time: 0.5 seconds
• Retry: None
• Operating Temperature:
– Min. ambient temperature rating is -40°F (-40°C)
– Max. ambient rating when used with 2.0A main valve
is 160°F (71°C)
• Relative Humidity: 0% to 95% non-condensing
• Johnson Controls:
G770RJA-1
• York: 025-27762-700 and
comparable ignition controls
ICM295
• Spark Ignition Control Module
• Microprocessor based
• For use with intermittent pilot boilers, furnaces
and other heating appliances
• Continuous spark until pilot flame established
• Push-on, high tension quick connect terminals
• Compatible with LP or Natural Gas
• Control Voltage: Line 24 VAC (18-30 VAC) @ 50/60Hz
• Prepurge: 0 or 10 seconds (system dependent)
• Retries: Continuous
• Operating Temperature: -40°F to 176°F
-40°C to 75°C
• Relative Humidity: 0% to 95% non-condensing
• Spark Frequency: 15Hz for 90 seconds, 10Hz
thereafter
• Carrier: LH33WZ510
ICM296
• Spark Ignition Control Module
• Microprocessor based
• For use with intermittent pilot boilers, furnaces
and other heating appliances
• 100% safety lockout
• Compatible with LP or Natural Gas
• Control Voltage: Line 24 VAC (18-30 VAC) @ 50/60Hz
• Prepurge: None
• Lockout: 5-6 minutes
• Retries: None
• Operating Temperature: -40°F to 176°F
-40°C to 75°C
• Relative Humidity: 0% to 95% non-condensing
• Relay Contact Rating: 1 amp @ 24 VAC
• Trail for Ignition: 90 seconds
• Flame Failure Response Time: 0.8 sec. max.
• Spark Frequency: 60 Hz
• Carrier: LH33WZ512A
ICM2901
• For use with intermittent pilot boilers, furnaces
and other heating appliances
• Microprocessor-based precision
• Monitors timing, trial for ignition, rollout switch,
flame sensing and lockout
• Remote flame sensing
• 100% lockout safety feature
• Compatible with LP or Natural Gas
• Control Voltage: Line 24 VAC (18-30 VAC) 50/60 Hz
• Anticipator Setting: 0.3A plus valve load @ 24 VAC
• Prepurge: None
• Trial for Ignition: 85 seconds
• Flame Failure Response Time: 0.5 seconds
• Retry: None
• Operating Temperature:
– Min. ambient temperature rating is -40°F (-40°C)
– Max. ambient rating when used with 2.0A main valve
is 160°F (71°C)
• Relative Humidity: 0% to 95% non-condensing
• ICM: 294
• Johnson Controls:
G770RJA-1
• York: 025-27762-700
and comparable ignition
controls.
ICM2902
• For use with intermittent pilot boilers, furnaces
and other heating appliances
• Microprocessor-based precision
• Monitors timing, trial for ignition, flame sensing
and lockout
• Remote flame sensing
• 100% lockout safety feature
• Compatible with LP or Natural Gas
• Status LED for fault codes to aid in
troubleshooting
• Control Voltage: Line 24 VAC (18-30 VAC) 50/60 Hz
• Anticipator Setting: 0.3A plus valve load @ 24 VAC
• Prepurge: 15 seconds
• Trial for Ignition: 60 minutes
• Lockout: 2 seconds
• Flame Failure Response Time: 0.5 seconds
• Status LED: See product label for error codes
• Operating Temperature:
– Min. ambient temperature rating is -40°F (-40°C)
– Max. ambient rating when used with 2.0A main valve
is 160°F (71°C)
• Relative Humidity: 0% to 95% non-condensing
• ICM: 293
• Johnson Controls:
G776
(63K2401, 41K8701,
69J3601) ignition controls
• Lennox: 30W33 ignition
control,
• Robertshaw: 735L
(18G91) or 745 (95H04)
ignition controls
315.233.5266
Phone
All features and specifications subject to change without notice.
Customer Service Fax
315.233.5282
Application Assistance
800.365.5525
Visit www.icmcontrols.com to find all
of our latest products, sell sheets and wiring diagrams
29