Specifications
Furnace Controls
Furnace Control Modules
ICM Control Features and Applications Specifications Replaces
ICM289
• Controls inducer fan motor, blower fan and monitors
limit switches
• Microprocessor based design
• Functions with all 24 VAC thermostats
• Voltage Range: Line (98-132 VAC) @ 60 Hz
• Cool blower: 20A @ 120 VAC
• Heat blower: 20A @ 120 VAC
• Inducer motor: 5A @ 120 VAC
• Cool blower On Delay: 1 second
• Cool blower Off Delay: 1 second
• Heat blower On Delay: 45 seconds
• Heat blower Off Delay: 90, 150, 210, 270 sec.
• Lennox:
Replaces all BCC1,
BCC2 and BCC3 circuit
boards, including 48K98
and 45K48.
ICM291
• Direct Spark Ignition (DSI) control board
• Microprocessor-based
• Controls combustion, blower and indoor motors; spark
ignitor and the gas valve
• Monitors timing, trial for ignition, flame sensing and
lockout
• 100% lockout safety feature
• Compatible with LP or Natural Gas
• Status LED for fault codes to aid in troubleshooting
• Control voltage: 24 VAC (18-30 VAC), 60 Hz
• Line voltage: 208/230 VAC, 60 Hz
• Power cons: 0.3A plus gas valve current @ 24 VAC
• Operating temp: -40°C (-40°F) to 75°C (176°F)
Timing
• Pre-purge: 45 seconds
• Trial for Ignition: 5+2 seconds
• Retry period: Every 20 seconds for 15 minutes
• Lockout: manual reset
• Post-purge: 45 seconds
Inputs
• Power: RT and C
• Thermostat interface: R, W and G
• Safety switches: RS, LS, and CS
• Combustion motor Hall Effect sensor
• Flame sensing
Outputs
• Spark
• Gas Valve: GV
• Combustion motor: CM
• Blower motor: BM
• Indoor fan motor: IFO
LED indicators
• Red LED: Steady ON- normal operation
Flashing – fault codes
• Carrier:
LH33WP003/3A
ICM292
• Direct Spark Ignition (DSI) control board
• Microprocessor-based
• Controls Induced Draft and indoor blower motors;
humidifier output, spark ignitor and gas valve
• Monitors timing, trial for ignition, flame sensing and
lockout
• 100% lockout safety feature
• Compatible with LP or Natural Gas
• Status LEDs for fault codes to aid in troubleshooting
• Control voltage: 24 VAC (18-30 VAC), 60 Hz
• Line voltage: 115 VAC, 60 Hz
• Power cons: 0.3A plus gas valve current at 24 VAC
• Operating temp: -40°C (-40°F) to 75°C (176°F)
Timing
• Pre-purge: 30 seconds
• Trial for ignition: 7 seconds
• Retries: 2 groups of 2, 30 seconds delay within the
group and 3 minutes delay between groups
• Lockout: 1 hour
• Post-purge: 90, 120, 160 and 180 seconds
Inputs
• Power: 24 VAC and COM
• Thermostat interface: R, W, Y and G
• System switches: Vent Pressure and Limit switches
(Main and Over-temperature switches in series)
• Flame Sensing
• Heat blower OFF delay: SW1 toggle switch
Outputs
• Spark: SE
• Gas Valve: GV
• Inducer draft motor: IDM
• Electric Air Cleaner: EAC
• Humidifier relay: HUM
• Heat/Cool relay: H/C
• Blower motor: FAN, COOL and HEAT speeds
LED indicators
• Power, green LED: PWR
• Status, green LED: OK
• Flame status, yellow LED: FLAME
• Rheem: 62-24140-04
ICM2801
• Controls vent motor, blower control, hot surface ignitor
and gas valve
• Monitors timing, trial for ignition, flame sensing and
lockout
• Microprocessor-based
• Reverse polarity protection
• 100% lockout safety feature
• Compatible with LP or Natural Gas
• Twinning compatible with another ICM2801 control
• Status LED for fault codes to aid in troubleshooting
• Line voltage: 98-132 VAC @ 60 Hz
• Ignitor: 5A, 120 VAC
• Cool blower: 10A, 2 HP, 240 VAC
• Heat: 5A, ½ HP, 250 VAC
• Inducer blower: 4A, 120 VAC
• Gas valve: 1A, 24 VAC
• York/Evcon:
7990-319P
315.233.5266
Phone
All features and specifications subject to change without notice.
Customer Service Fax
315.233.5282
Application Assistance
800.365.5525
Visit www.icmcontrols.com to find all
of our latest products, sell sheets and wiring diagrams