Specifications

Furnace Controls
ICM offers low cost, form, fit and functional replacement furnace controls for many popular OEM
models. Our furnace controls come standard with many safety features including 100% gas shutoff in
case of ignition failure.
Furnace Control Modules
ICM Control Features and Applications Specifications Replaces
ICM280
Microprocessor-based fan blower
Inducer fan outputs
Hot surface ignitor output
Flame sensor input
Gas valve output
Status LED for fault codes
Twinning compatible with another ICM280 board
Voltage: Line (98-132 VAC) @ 60 Hz
Fan: 2 HP @ 240 VAC
Inducer motor: 7 amps @ 250 VAC
Gas valve: 1 amps @ 24 VAC
Ignitor: 5 amps @ 120 VAC
Goodman: B1809906
B1809908, B1809910
B1809913, B1809913S
UTEC: 1012-933D
Texas Instruments:
41F-5
White-Rodgers:
50T35-730, 50T35-743
ICM281
Control gas valve, ignitor, blower motor, inducer,
humidifier and air cleaner
Microprocessor-based
Designed for 100% gas shutoff in case of ignition failure
Model selection of 80+ and 90+ furnace operation
Reverse polarity protection
Secondary brownout voltage protection
Heating and cooling fan functions in response to
standard thermostat
Provides diagnostic LEDs to aid in troubleshooting
Twinning compatible with another ICM281 board
Voltage: Line (98-132 VAC) @ 60 Hz
Operating temperature: -40°C to 176°F
Ignitor: 5A @ 120 VAC
Cool blower: 30A, 2HP, 240 VAC
Heat: 5A, 1/2 HP, 240 VAC
Inducer motor: 4A, FLA-8.0 LRA @ 120 VAC
Gas valve: 1.5A @ 30 VAC
Carrier:
CES0110057-00
CES0110057-01
CES0110057-02
ICM282A
Control gas valve, ignitor, blower motor, inducer,
humidifier and air cleaner
Microprocessor-based
Designed for 100% gas shutoff in case of ignition failure
Reverse polarity protection
Secondary brownout voltage protection
Heating and cooling fan functions in response to
standard thermostat
Provides diagnostic LEDs to aid in troubleshooting
Includes adapter harness (not shown)
Twinning compatible with another ICM282A board
Voltage: Line (98-132 VAC) @ 60 Hz
Operating temperature: -40°C to 176°F
Ignitor: 5A @ 120 VAC
Cool blower: 30A, 2HP, 240 VAC
Heat: 5A, 1/2 HP, 240 VAC
Inducer motor: 4A, FLA-8.0 LRA @ 120 VAC
Gas valve: 1.5A @ 30 VAC
Carrier:
HK42FZ004,
HK42FZ007
HK42FZ008
HK42FZ009
HK42FZ011
HK42FZ013
HK42FZ016
325878-751
ICM284
Microprocessor based
Controls vent motor, blower control, hot surface ignitor
and gas valve
Monitors timing, trial for ignition, flame sensing and
lockout
Diagnostic LEDs to aid in testing/troubleshooting
Line voltage: 208 VAC @ 60 Hz
Ignitor: 5A resistive @ 208 VAC
Heat blower: 10A, .5 HP, 250VAC
Cool blower: 30A, 2HP, 240 VAC
Inducer Motor: 4A, 120 VAC
Gas Valve: 4A @ 24 VAC
Compressor: 5A resistive @ 24 VAC
York: SI-03101280000
ICM286
Microprocessor-based precision
Controls inducer and blower fan motors, hot surface
ignitor, and gas valve
Monitors timing, trial for ignition, flame sensing,
pressure and limit switches, and lockout
Designed for 100% gas shutoff in case of ignition failure
Reverse polarity protection
Twinning compatible with another ICM286 control board
Compatible with LP or natural gas
Diagnostic LED to aid in testing/troubleshooting
Trial for Ignition: 7 seconds
Pre-purge Time: 15 seconds
Ignitor Warm Up Time: 7 seconds
Post-Purge Time: 15 seconds
Total Trials for Ignition: 3 (auto reset after 1 hour)
Heat Blower On: 30 seconds
Heat Blower Off: Selectable 90/120/150/180 seconds
Fan (Heat) On/Off Delay: 1 second
Cool On: 5 seconds
Cool Off: 45 seconds
Goodman:
PCBBF112S,
B18099-26S,
0130F00005S
ICM287
Microprocessor based
Controls inducer and blower control,
Monitors timing and gas valve
Diagnostic LEDs to aid in testing/troubleshooting
Line voltage: 120 VAC @ 60 Hz
Control voltage: 24 VAC @ 60 Hz
Heat blower: 10A, 120 VAC
Cool blower: 30A, 120 VAC
Inducer blower: 30A, 120 VAC
Goodman: B18099-04
ICM288
Microprocessor-based precision
Monitors pressure, roll-out and limit switches
Controls gas valve, inducer draft motor, circulating
blower and hot surface ignitor.
Reverse polarity detection
Twinning compatible with another ICM288 board
Diagnostic LEDs to aid in testing/troubleshooting
Voltage Range: Line (98-132 VAC) @ 60Hz
Ignitor: 5A, 120 VAC
Cool Blower: 10A, 2HP, 240 VAC
Heat: 5A, ½ HP, 250 VAC
Inducer Blower: 4A, 120 VAC
Gas Valve: 1A, 24 VAC
Humidifier Motor: 0.5A, 24 VAC
Electronic Air Cleaner: 1A, 120 VAC
Rheem: 62-24084-82
315.233.5266
Phone
All features and specifications subject to change without notice.
Customer Service Fax
315.233.5282
Application Assistance
800.365.5525
Visit www.icmcontrols.com to find all
of our latest products, sell sheets and wiring diagrams