Specifications
Motor Starters
ICM860 - Voltage Sensing
ICM’s differential voltage sensing products employ patented circuitry which monitors differential compressor auxiliary
voltage, determines the state of the motor and precisely engages and disengages the start capacitor.
A timed safety circuit is provided in the event the motor fails to start within 2 seconds.
ICM Controls Features and Applications Specifications Replaces
ICM860
• Increases starting torque up to 500%
• Ensures precise starts
• Reduces inventory
• Not affected by ambient temperature
• Recycles Instantly (less than one second)
• Dual voltage operation: either 115 or 240 VAC motors
• Fuse protection
• Not affected by voltage or current fluctuations
• Voltage: 90-277 VAC
• Maximum input voltage: 390 VAC
• Operating temperature range:
-40˚C to +65˚C
• Capacitor: 88-106 Mfd. 330 V
• Range: 1/12 to 5 HP applications
• Supco:
SPP-5E
SPP-6E
Wiring Diagram
Start
To
Compressor
Run
Run Capacitor
System Diagram
For product dimensions,
please visit our website at
www.icmcontrols.com
ICM Controls has been delivering
award-winning ingenuity and
innovation to the HVACR industry
for nearly 30-years!
315.233.5266
Phone
All features and specifications subject to change without notice.
Customer Service Fax
315.233.5282
Application Assistance
800.365.5525
Visit www.icmcontrols.com to find all
of our latest products, sell sheets and wiring diagrams
22