Specifications

Motor Speed Controls
Comfort Control Center
Applications Wiring Diagram
The award-winning CC750 Comfort Control Center works with your existing
single-phase A/C or Heat Pump to more effectively remove moisture from the air.
Provides enhanced comfort and improved indoor air quality with greater system
efficiencies. Generates warmer air discharge temps for winter months in heat
pump applications.
Converts an inverter or standard grade PSC or shaded pole motor to a variable
speed motor. Simple, menu driven programming gives the installer the ability to
fine-tune key parameters that establish a latent and sensible cooling ratio best
suited for the unique conditions of each installation. Also provides warmer air
discharge temperatures for heat pumps during winter months.
Mode of Operation
A variable frequency/variable voltage fan motor speed control, the CC750 varies the blower speed
based on the evaporator and return air temperature. A field adjustable temperature differential between
the evaporator and the return air duct is maintained by controlling blower speed. A simple to use, menu
driven program lets the installer establish a latent and sensible cooling ratio to best meet the specific
environmental conditions unique to each install.
ICM Control Features and Applications Specifications
ICM CC750
Converts an inverter or standard grade PSC or shaded pole motor to a
variable speed motor
Field programmable
Varies the air flow based on delta T
Mounts in or out of air handler
Motor lubrication algorithm
Inverter bypass
Over-current protection
Standard thermostat interface
Available in 115 VAC (CC750-115) and 230 VAC (CC750-230)
Replaces: N/A
Ratings
Nominal 24 VAC inputs (±25%): 18-30 VAC RMS absolute
Power consumption: 10 watts typical
Line Ratings: Nominal, 115 VAC RMS
Inverter operation: 95-135 VAC RMS absolute
Bypass operation: 85-145 VAC RMS absolute
Maximum inverter amps: 10 amps RMS
Maximum bypass amps: 20 amps (60 Hz)
Line Ratings: Nominal 208-230 VAC RMS
Inverter operation: 180-264 VAC RMS absolute
Bypass operation: 170-264 VAC RMS absolute
Maximum inverter amps: 8.5 amps RMS
Maximum bypass amps: 10 amps (60 Hz)
Fan Coil Relay Controls
ICM Control Features and Applications Specifications
ICM6200
Ability to operate line voltage 3-speed fan motor with low voltage controls
Compatible with 4-pipe, 2 pipe, HP, auto-changeover
20 VA 24 VAC power supply
Suitable for 1/8 HP motors
1/4” Quick connect terminals
Mounts with standard 3” track
InputTransformer Primary: 115 VAC; 50-60 Hz
Fan Inputs HI, MED, LOW: nominal 17mA @ 24 VAC
Heat & Cool: 1.5A @ 24 VAC
Output Transformer Secondary: 24 VAC; 20 VA
Relay outputs H, M, L: 1/8HP @ 115 VAC,
10A @ 240 VAC resistive max.
Heat & Cool Valves: 1.5A @ 24 VAC
Replaces: Honeywell W6380B, BSR/Xactone FC/H-2
ICM6201
Ability to operate line voltage 3-speed fan motor with low voltage controls
Ability to operate line voltage electric heating element with low voltage
controls
Compatible with 4-pipe, 2 pipe, aquastat autochangeover, and heat pump
20 VA 24 VAC power supply
Suitable for 1/8 HP motors
Screw terminal receptacles
Mounts with standard 3” track
InputTransformer Primary (L1 & L2): 115 VAC; 50-60 Hz
HI, MED, LOW (8, 7, 6): Nominal 17 mA @ 24 VAC
Inputs 1, 2, 3, 4, 5, Aqua Heat & Cool: 1.5A @ 24 VAC
Output Transformer Secondary: 24 VAC; 20 VA
Relay Outputs H, M, L: 1/8 HP @ 115 VAC,
10A @ 240 VAC resistive
HTR Output: 30A @ 240 VAC resistive
Heat & Cool Valves: 1.5A @ 24 VAC
Replaces: Honeywell W6380B, BSR/Xactone FC/H-1
Fan Coil Relay Control Boards
Fan Safety Alarm
ICM Control Features and Applications Specifications
ICM6100
Fan safety alarm circuit
Outputs provided ensure that a DDC controller can determine the root
cause of a shutdown.
Dip switch to bypass inputs not in use.
Ideal for Air Handling Unit safety-shutdown.
2.75” mounting track provided
Input: 24 VAC; 50-60 Hz (4A max)
Output Relay outputs (6): 2A @ 24 VAC/DC per output
Master relay 24 VAC (2): 1.5A @ 24 VAC per output
Master relay dry contacts: 10A @ 250 VAC
Alarm status: Green LED ON = Activated
Red LED ON = Not Activated
Replaces: Functional Devices: RIBMNLB-6
Fan Safety Alarm
315.233.5266
Phone
All features and specifications subject to change without notice.
Customer Service Fax
315.233.5282
Application Assistance
800.365.5525
Visit www.icmcontrols.com to find all
of our latest products, sell sheets and wiring diagrams
19