Specifications
Motor Speed Controls
Comfort Control Center
Applications Wiring Diagram
The award-winning CC750 Comfort Control Center works with your existing
single-phase A/C or Heat Pump to more effectively remove moisture from the air.
Provides enhanced comfort and improved indoor air quality with greater system
efficiencies. Generates warmer air discharge temps for winter months in heat
pump applications.
Converts an inverter or standard grade PSC or shaded pole motor to a variable
speed motor. Simple, menu driven programming gives the installer the ability to
fine-tune key parameters that establish a latent and sensible cooling ratio best
suited for the unique conditions of each installation. Also provides warmer air
discharge temperatures for heat pumps during winter months.
Mode of Operation
A variable frequency/variable voltage fan motor speed control, the CC750 varies the blower speed
based on the evaporator and return air temperature. A field adjustable temperature differential between
the evaporator and the return air duct is maintained by controlling blower speed. A simple to use, menu
driven program lets the installer establish a latent and sensible cooling ratio to best meet the specific
environmental conditions unique to each install.
ICM Control Features and Applications Specifications
ICM CC750
• Converts an inverter or standard grade PSC or shaded pole motor to a
variable speed motor
• Field programmable
• Varies the air flow based on delta T
• Mounts in or out of air handler
• Motor lubrication algorithm
• Inverter bypass
• Over-current protection
• Standard thermostat interface
• Available in 115 VAC (CC750-115) and 230 VAC (CC750-230)
• Replaces: N/A
Ratings
• Nominal 24 VAC inputs (±25%): 18-30 VAC RMS absolute
• Power consumption: 10 watts typical
Line Ratings: Nominal, 115 VAC RMS
• Inverter operation: 95-135 VAC RMS absolute
• Bypass operation: 85-145 VAC RMS absolute
• Maximum inverter amps: 10 amps RMS
• Maximum bypass amps: 20 amps (60 Hz)
Line Ratings: Nominal 208-230 VAC RMS
• Inverter operation: 180-264 VAC RMS absolute
• Bypass operation: 170-264 VAC RMS absolute
• Maximum inverter amps: 8.5 amps RMS
• Maximum bypass amps: 10 amps (60 Hz)
Fan Coil Relay Controls
ICM Control Features and Applications Specifications
ICM6200
• Ability to operate line voltage 3-speed fan motor with low voltage controls
• Compatible with 4-pipe, 2 pipe, HP, auto-changeover
• 20 VA 24 VAC power supply
• Suitable for 1/8 HP motors
• 1/4” Quick connect terminals
• Mounts with standard 3” track
Input • Transformer Primary: 115 VAC; 50-60 Hz
• Fan Inputs HI, MED, LOW: nominal 17mA @ 24 VAC
• Heat & Cool: 1.5A @ 24 VAC
Output • Transformer Secondary: 24 VAC; 20 VA
• Relay outputs H, M, L: 1/8HP @ 115 VAC,
10A @ 240 VAC resistive max.
• Heat & Cool Valves: 1.5A @ 24 VAC
Replaces: Honeywell W6380B, BSR/Xactone FC/H-2
ICM6201
• Ability to operate line voltage 3-speed fan motor with low voltage controls
• Ability to operate line voltage electric heating element with low voltage
controls
• Compatible with 4-pipe, 2 pipe, aquastat autochangeover, and heat pump
• 20 VA 24 VAC power supply
• Suitable for 1/8 HP motors
• Screw terminal receptacles
• Mounts with standard 3” track
Input • Transformer Primary (L1 & L2): 115 VAC; 50-60 Hz
• HI, MED, LOW (8, 7, 6): Nominal 17 mA @ 24 VAC
• Inputs 1, 2, 3, 4, 5, Aqua Heat & Cool: 1.5A @ 24 VAC
Output • Transformer Secondary: 24 VAC; 20 VA
• Relay Outputs H, M, L: 1/8 HP @ 115 VAC,
10A @ 240 VAC resistive
• HTR Output: 30A @ 240 VAC resistive
• Heat & Cool Valves: 1.5A @ 24 VAC
Replaces: Honeywell W6380B, BSR/Xactone FC/H-1
Fan Coil Relay Control Boards
Fan Safety Alarm
ICM Control Features and Applications Specifications
ICM6100
• Fan safety alarm circuit
• Outputs provided ensure that a DDC controller can determine the root
cause of a shutdown.
• Dip switch to bypass inputs not in use.
• Ideal for Air Handling Unit safety-shutdown.
• 2.75” mounting track provided
Input: 24 VAC; 50-60 Hz (4A max)
Output • Relay outputs (6): 2A @ 24 VAC/DC per output
• Master relay 24 VAC (2): 1.5A @ 24 VAC per output
• Master relay dry contacts: 10A @ 250 VAC
• Alarm status: Green LED ON = Activated
Red LED ON = Not Activated
Replaces: Functional Devices: RIBMNLB-6
Fan Safety Alarm