Specifications

Motor Protection Controls
3-Phase Temperature Monitor
ICM Control Features and Applications Specifications Replaces
ICM441
Protects Against:
Under voltage
Over temperature
Power interruptions
Rapid short cycling
Shorted temperature sensor
Open temperature sensor
Control duty, SPST relay layout
Anti-short cycle time delay, 4 minutes (nominal)
1-second manual bypass
Voltage: 120 or 208/240 VAC
Frequency: 50-60 Hz
Output:
Relay: SPST
N.O.: 6 amps resistive
Dimensions: 3.25” x 3” x 1.25”
Bristol: 241680
Copeland:
071-0376-01, 071-0376-02
071-0397-00, 071-0397-01
071-0424-00, 071-0424-01
071-9800-00, 071-9800-01
Mars:
37300, 37302. 37304,
37306, 37322
Texas Instruments:
15AA1600 B, 15AA1600 C
15AA1603 B, 15AA1603 C
31AA1600 E, 31AA1606 E
Single Phase Motor Protection
ICM Control Features and Applications Specifications Replaces
ICM491
Low cost single phase motor protection
Built in anti-short cycle protection
Detects high/low voltage conditions
Helps prevent rapid system recycling
LED indicators:
• Green for normal conditions
• Red for fault
Heavy duty SPDT, isolated relay output
Interrogation delay prevents nuisance trips: 5 seconds
Voltage: 95-270 VAC
Output:
Relay: SPDT
N.C./N.O.: 5 amps
Time delay range: Adjustable
6-600 seconds
Dimensions: 3.25” x 3” x 1.25”
A-1: EAC-401, EAC-402
EAC-403, EAC-404
Diversified: CV-100-RS
CV-200-RS15
CV-200-RS20
Wagner/DiversiTech:
DSP-1
ICM492
Protects against over and under voltage, and rapid short
cycling caused by transient faults and power interruptions
Easy-view, backlit digital display
RMS voltage monitoring
Adjustable voltage set point
Adjustable over voltage setting
Adjustable under voltage setting
Adjustable anti-short cycle time delay
Adjustable response time
Control mode
5-fault memory
Universal line voltage input
Heavy duty SPDT relay output
Universal control voltage input (for integrating a thermostat)
User adjustable settings:
Voltage set point: 80-300 VAC
Anti-short cycle time delay: 0-720 sec.
Over voltage setting: 5-25%
Under voltage setting: 5-25%
Control mode: On and Off
Response time: 0.1-10 seconds
Inputs:
Line voltage: 80-300 VAC
Frequency: 50-60 Hz
Accuracy: ±2%
Low power consumption:
• Maximum 50 mA @ 120V
• Maximum 100 mA @ 240V
Control voltage: 24-240 VAC
Output:
Type: Dry relay contacts
Form: SPDT
Relay contact ratings:
N.C. contacts: 10A resistive
@ 277 VAC
N.O. contacts: 10A resistive
@ 277 VAC
Mechanical:
Case dimensions: 3”L x 3.2”W x 1.35”H
Unit weight: 0.36 lbs.
Wagner/DiversiTech:
DSP-1
ICM515
Easy installation
Low cost, high performance
Weatherproof housing
Rugged, reliable
Protects against:
• Lightning power surges
• Voltage surges from air conditioners, generators, motors
Service voltage: 120-240 VAC,
single phase
Max. surge current: 24,000 amps
Max. energy dissipation: 240 Joules
Installation point:
• Electrical panel
• Electrical disconnect
AC protection modes: Line-line,
line-ground
Dimensions: 1.75” x 1.62” x 0.75”
Ditek: DTK-120-240CM
Supco: SCM
ICM516
Type 2 surge protective device
UL Listed
Easy installation
Low cost, high performance
Rugged, reliable
Protects against:
• Lightning power surges
• Voltage surges from air conditioners, generators, motors
Limited Lifetime Protection Warranty
Service voltage: 120-240 VAC,
single phase
Max. surge current: 100,000 amps
Max. energy dissipation: 1,020 Joules
Installation point:
• Electrical panel
• Electrical disconnect
AC protection modes: Line-line,
line-ground
Dimensions: 2.75” x 4.75” x 1.75”
Supco: SCM Plus,
SCM150
315.233.5266
Phone
All features and specifications subject to change without notice.
Customer Service Fax
315.233.5282
Application Assistance
800.365.5525
Visit www.icmcontrols.com to find all
of our latest products, sell sheets and wiring diagrams
17