EP-300 SERIES PUMP INSTALLATION, OPERATION AND SERVICE MANUAL
18
7.4 Vertical Venting
The vent material must be either heat treated alumi-
nized tubing 6" (15 cm) O.D. (P/N E0009105) or sin-
gle wall flue pipe minimum 26 Ga.). Vent length
should be limited to less than 20' (6 m). If using vent
lengths greater than 20' (6 m), condensation will form
in the vent pipe. Insulation and additional sealing
measures will be required. Length of flue pipe is
equal to total of vertical and horizontal length.
7.5 Venting Accessories
NOTE: 4" (10 cm) accessories may only be used on
the inlet side of the EP-301 pump.
See Page 21, Section 9 for venting accessories.
FIGURE 17: Vertical Venting
Tee
6" (15 cm)
Roof
Drain Tube
Vent Cap
2' (61 cm)
Minimum
Drain Cap
6" (15 cm)
Thimble
to drain
Description Part Number
Tee 6" (15 cm) 01330204
Vent Cap 6" (15 cm) 90502302
Drain Cap 6" (15 cm) 02718852