Service manual

SECTION 7: VENTING
17
FIGURE 16: Horizontal Venting
10' (3 m) Maximum and 1 Elbow
Thimble
Vent Terminal
Tjernlund VH1-
6" (15 cm)
or Equivalent
(Not Included)
6" (15 cm)
Bird Screen
(Included)
18" (46 cm) Minimum -
40" (102 cm) Maximum
10' (3 m) Maximum and 1 Elbow
6" (15 cm)
Band Clamp
Single Wall Pipe/Tube 6" (15 cm)
Pitch single wall pipe
downward away from pump
1/4" every 10' (3 m).
NOTE: See Page 21, Section 9 for common
venting components and part numbers.
Description Part Number
Bird Screen 6" (15 cm) 01397400
Pump Boot 6" (15 cm) 91412802
Band Clamp 6" (15 cm) 91913703
Thimble 90505600
Vent Terminal 6" (15 cm) 90502101
(Not required on
non-combustible